Case: T06FR02773

Parcel: 107150140


Addresses:

614 E GLENN ST

Inspection Status: Correction Required

Inspection History: INSP - AST/UST

Date Description Inspector Results Comments
11/21/2006 INSP - AST/UST Correction Required Inspected ASTs on premises
3 x 120 gallon- New Oil
1 x 240 gallon- New Oil
1 x 1000 gallon- Used Oil
Corrections required are:
1. combustible liquid placards on all tanks
2. emergency venting for the waste oil, 1-120 gal tank
3. secondary containment for 1-120 gal tank