Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

11/21/2006

Applicant:

GARY & PENNY'S LLC

Description:

AST Inspection

Outstanding Inspections

Case Number: T06FR02773
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
11/21/2006 INSP - AST/UST JLANGEJA Correction Required Inspected ASTs on premises 3 x 120 gallon- New Oil 1 x 240 gallon- New Oil 1 x 1000 gallon- Used Oil Corrections required are: 1. combustible liquid placards on all tanks 2. emergency venting for the waste oil, 1-120 gal tank 3. secondary containment for 1-120 gal tank