Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T06FR02728
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/22/2006 | INSP - FULL | Approved | approved | |
11/08/2006 | INSP - FULL | Violation | 1). Smoke detectors test log shall be submitted with all smokes detectors tested and repaired. IFC 901.6 2). Fire Dept access is to sprinkler connections is blocked by weeks and auto. Sign shall be posted. FIRE DEPT ACCESS. DO NOT BLOCK. IFC 508.5.4 3). Chapter wall, mechanical room. Repair wall with rated material. IFC 703.1 4). Chapter room. Repair exit sign. IFC 1026.3 5). Emergency illumination power shall be provided for all hallways. IFC 1`026.5 6). Remove all material under outside stairs. IFC 305 |