Inspection Status: Approved
Inspection History: INSP - AST/UST
| Date |
Description |
Inspector |
Results |
Comments |
| 09/18/2006 |
INSP - AST/UST |
|
Approved |
1000 gallon fuel AST was permitted for removal. Southwest Hazard Control (Eric) inerted the AST with 75# CO2. It purged at <3% O2. All openings were plugged and a 1/4" hole was placed in a bung to prevent overpressurization. All piping was removed. Catclaw Contractors (Aaron Holmes) lifted the tank into a trailor from Tucson Iron & Metal. The truck was placarded appropriately prior to leaving the site. AST is OOS. |