Case: T06FR02587

Parcel: 13215002A


Addresses:

797 E AJO WY

Inspection Status: Approved

Inspection History: INSP - AST/UST

Date Description Inspector Results Comments
09/18/2006 INSP - AST/UST Approved 1000 gallon fuel AST was permitted for removal. Southwest Hazard Control (Eric) inerted the AST with 75# CO2. It purged at <3% O2. All openings were plugged and a 1/4" hole was placed in a bung to prevent overpressurization. All piping was removed. Catclaw Contractors (Aaron Holmes) lifted the tank into a trailor from Tucson Iron & Metal. The truck was placarded appropriately prior to leaving the site. AST is OOS.