Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

09/18/2006

Applicant:

CITY OF TUCSON

Description:

AST removal

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR02587
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/18/2006 INSP - AST/UST JLANGEJA Approved 1000 gallon fuel AST was permitted for removal. Southwest Hazard Control (Eric) inerted the AST with 75# CO2. It purged at <3% O2. All openings were plugged and a 1/4" hole was placed in a bung to prevent overpressurization. All piping was removed. Catclaw Contractors (Aaron Holmes) lifted the tank into a trailor from Tucson Iron & Metal. The truck was placarded appropriately prior to leaving the site. AST is OOS.