Inspection Status: Violation
Inspection History: VIOL - MOTOR FUEL DISPENSING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/08/2006 | VIOL - MOTOR FUEL DISPENSING | Violation | IFC 2203.2- An approved, clearly identifiable sign shall be provided at the emergency disconnect. It shall read: "EMERGENCY FUEL SHUTOFF". | |
| 09/08/2006 | VIOL - MOTOR FUEL DISPENSING | Violation | ifc 2205.2.2- Automatic-closing emergency shutoff valves shall be checked not less than once per year by manually tripping the hold-open linkage. | |
| 09/08/2006 | VIOL - MOTOR FUEL DISPENSING | Violation | IFC 2206.2.1.1- Accurate daily inventory records shall be maintained for indication of possible leakage from tanks and piping. I will need documentation for the following tests; 1. line leak detection 2. tank tightness |