Description:

Tank Inspection

Outstanding Inspections

Case Number: T06FR02545
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
09/08/2006 INSP - AST/UST JLANGEJA Correction Required This is from an original permit issued in 2003. The previous owner never got a final on the tanks. One tank has been converted to diesel. Due to the length of time, a tank tightness and line leak detection test is required. LPG has been removed.
09/08/2006 VIOL - MOTOR FUEL DISPENSING JLANGEJA Violation IFC 2203.2- An approved, clearly identifiable sign shall be provided at the emergency disconnect. It shall read: "EMERGENCY FUEL SHUTOFF".
09/08/2006 VIOL - MOTOR FUEL DISPENSING JLANGEJA Violation ifc 2205.2.2- Automatic-closing emergency shutoff valves shall be checked not less than once per year by manually tripping the hold-open linkage.
09/08/2006 VIOL - MOTOR FUEL DISPENSING JLANGEJA Violation IFC 2206.2.1.1- Accurate daily inventory records shall be maintained for indication of possible leakage from tanks and piping. I will need documentation for the following tests; 1. line leak detection 2. tank tightness
09/28/2006 INSP - REINSPECTION JLANGEJA Continued The emergency shutoff has been signed appropriately. Vista Maint. was there this morning to perform the service work. They will send me the work order.