Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/20/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 2003 IFC 605.1 605.1 Abatement of electrical hazards Exposed electrical wires , covers, and panels locked. Undergroud romex can be above 7’ and not in conduit, if protected from UV light and damage. 1) REPAIR OUTLET AND WIRES IN STORAGE ROOM E WALL. 2) REMOVE SURGE STRIP THROUGH WALL. HARD WIRE OUTLET FOR SURGE PROTECTOR TO PLUG INTO. |
|
| 02/20/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 2003 IFC TFC 605.5 Extension cords Grounds, used as permanent wiring, run under carpet, attached to walls can be replaced w/ power strip that has overcurrent protection 1) REMOVE EXTENSION CORD IN SW BEDROOM 2) REMOVE EXTENSION CORD ON BACK PORCH |
|
| 02/20/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 2003 IFC 603.1 & 316.2 Fuel fired appliances and house cleaning. Furnaces, dryer and hot water heaters are all heat sources and must bemaintained and cleaned. NOT STORAGE IN FRONT OF HOTWATER HEATER. |
|
| 02/20/2007 | VIOL - BUILDING SVCS & SYSTEMS | Approved |