Inspection Status: Violation

Inspection History: VIOL - PRECAUTION AGAINST FIRE

Date Description Inspector Results Comments
12/05/2006 VIOL - PRECAUTION AGAINST FIRE Violation IFC 2003 304.1.2 Excessive combustibles
Must be safe for non self preserving residents. Weeds over 6” high, Look at alleys and around gas meters. Laddering of vegetation to home
1. CLEAR WEEDS 3 FEET AWAY FROM HOUSE.
2. REMOVE VEGETATION FROM ELECTRICAL PANEL
12/05/2006 VIOL - PRECAUTION AGAINST FIRE Violation IFC 2003 316.1 General.
The hood system is part of the cooking appliance and must be kept free of grease. If this has a problem, then there be others.
1. EXCESS GREASE AROUND STOVE. NO VENT
12/05/2006 VIOL - PRECAUTION AGAINST FIRE Violation IFC 2003 316.1 & 605.7 Electrical and gas appliances
Electrical needs UL listing. Check gas connections
1. STOVE NOT INSTALLED PROPERLY.
2. NO BACK SPASH PROTECTION AND VENTILATION
3. ELECTRICAL CORD TO CLOSE TO OPEN FLAME
4. CABINET ABOVE RANGE IS UNPROTECTED FROM OPEN FLAME
12/05/2006 VIOL - PRECAUTION AGAINST FIRE Violation IFC 2003 603.1 & 316.2 Fuel fired appliances and house cleaning.
Furnaces, dryer and hot water heaters are all heat sources and must bemaintained and cleaned.
1. REMOVE WOODEN STRUCTURE FROM AROUND HOT WATER HEATER AND REPLACE WITH METAL STRUCTURE.
2. REPLACE PLASTIC DRYER VENT HOSE WITH METAL FLEX TUBE.