Description:
FIRE INSPECTION CHECK LIST USED
Outstanding Inspections
Case Number: T06FR02419
Case Status: REFERRED
Case Description: INSPECTION
Total Outstanding Inspections - 10
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/05/2006 | INSP - FULL | MWAINWRI | Violation | ASL LIC FOR 7. ONE YR. INSP. |
| 12/05/2006 | VIOL - ADMINISTRATION | MWAINWRI | Violation | IFC 2003 102.3 Change of use of a building Must have it posted, must have correct occupancy type, and licensed amount must match occupancy class. R3 or R4 Date of C/O defines TFC used for regulation. 1. POST C OF O |
| 12/05/2006 | VIOL - PRECAUTION AGAINST FIRE | MWAINWRI | Violation | IFC 2003 304.1.2 Excessive combustibles Must be safe for non self preserving residents. Weeds over 6” high, Look at alleys and around gas meters. Laddering of vegetation to home 1. CLEAR WEEDS 3 FEET AWAY FROM HOUSE. 2. REMOVE VEGETATION FROM ELECTRICAL PANEL |
| 12/05/2006 | VIOL - PRECAUTION AGAINST FIRE | MWAINWRI | Violation | IFC 2003 316.1 & 605.7 Electrical and gas appliances Electrical needs UL listing. Check gas connections 1. STOVE NOT INSTALLED PROPERLY. 2. NO BACK SPASH PROTECTION AND VENTILATION 3. ELECTRICAL CORD TO CLOSE TO OPEN FLAME 4. CABINET ABOVE RANGE IS UNPROTECTED FROM OPEN FLAME |
| 12/05/2006 | VIOL - PRECAUTION AGAINST FIRE | MWAINWRI | Violation | IFC 2003 316.1 General. The hood system is part of the cooking appliance and must be kept free of grease. If this has a problem, then there be others. 1. EXCESS GREASE AROUND STOVE. NO VENT |
| 12/05/2006 | VIOL - PRECAUTION AGAINST FIRE | MWAINWRI | Violation | IFC 2003 603.1 & 316.2 Fuel fired appliances and house cleaning. Furnaces, dryer and hot water heaters are all heat sources and must bemaintained and cleaned. 1. REMOVE WOODEN STRUCTURE FROM AROUND HOT WATER HEATER AND REPLACE WITH METAL STRUCTURE. 2. REPLACE PLASTIC DRYER VENT HOSE WITH METAL FLEX TUBE. |
| 12/05/2006 | VIOL - BUILDING SVCS & SYSTEMS | MWAINWRI | Violation | IFC 2003 605.1 Abatement of electrical hazards Exposed electrical wires , covers, and panels locked. Undergroud romex can be above 7’ and not in conduit, if protected fromUV light and damage. 1. REPLACE OUTSIDE LIGHT FIXTURE BY OUTSIDE KITCHEN EXIT. 2. REMOVE LIGHT FIXTURE IN CENTER OF PORCH ON NORTH SIDE OF HOUSE. 3. FILL IN EMPTY BREAKER SPACES IN ELECTRICAL PANEL. 4. LIGHT ABOVE WASHER MUST HAVE A COVER. |
| 12/05/2006 | VIOL - BUILDING SVCS & SYSTEMS | MWAINWRI | Violation | IFC 2003 605.4 Multi-plugs and power-taps UL listed,No end to end, home made 1. REMOVE MUTIPLUG ADAPTERS AND IN VICTORS ROOM. |
| 12/05/2006 | VIOL - FIRE PROTECTION SYSTEMS | MWAINWRI | Violation | IFC 2003 907.2.10 Smoke alarms Check for operation and location. Min. is bedrooms and hallway 1. REPAIR OR REPLACE SMOKE ALARMS IN MIDDLE BEDROOM AND NEED A SMOKE ALARM IN PRIVATE BEDROOM. |
| 12/05/2006 | VIOL - MEANS OF EGRESS | MWAINWRI | Violation | IFC 2003 31. TFC 1026.5 Emergecy ligting Required in Group R if over 10, and must have 2 exits. Exception: If eachsleeping room has a direct exit to the outside. 1. REPAIR EMERGENCY LIGHTING IN BOTH HALLWAYS. |