Case: T06FR02332

Parcel: 11515008A


Addresses:

865 W GRANT RD

Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
07/27/2006 VIOL - BUILDING SVCS & SYSTEMS Approved TFC 605.4 Multiple misuse of unapproved multiplug adapters in the following areas:
1.) in the office area .
2.) throughout the main shop area.
07/27/2006 VIOL - BUILDING SVCS & SYSTEMS Approved TFC 605.4.1 Power taps: Approved power taps shall be of the polarized or ground type equipped with overcurrent protection
07/27/2006 VIOL - BUILDING SVCS & SYSTEMS Approved TFC 605.5 Extension / flex cord misuse throughout the main shop area shall be discontinued . Only approved power strip bars are allowed.
07/27/2006 VIOL - BUILDING SVCS & SYSTEMS Approved TFC 605.6 Cover plates for switches and electrical outlet boxes shall be provided in the following areas:
1.) office, west wall
2.) power outlet for microwave.
3.) shop area, next to lg. shop vac.
07/27/2006 VIOL - BUILDING SVCS & SYSTEMS Approved TFC 605.3 A minimum of 36 inch clearance shall be provided for the surrounding area of the any electrical panel.