Case: T06FR02332
Case Details
Entered Date:
07/27/2006
Applicant:
STEINMANN ROBERT J & JENNIFER CP/RS
Description:
Full Inspection
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR02332
Case Description: INSPECTION
Total Completed Inspections - 6
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/27/2006 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.3 A minimum of 36 inch clearance shall be provided for the surrounding area of the any electrical panel. |
| 07/27/2006 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.6 Cover plates for switches and electrical outlet boxes shall be provided in the following areas: 1.) office, west wall 2.) power outlet for microwave. 3.) shop area, next to lg. shop vac. |
| 07/27/2006 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.5 Extension / flex cord misuse throughout the main shop area shall be discontinued . Only approved power strip bars are allowed. |
| 07/27/2006 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.4.1 Power taps: Approved power taps shall be of the polarized or ground type equipped with overcurrent protection |
| 07/27/2006 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.4 Multiple misuse of unapproved multiplug adapters in the following areas: 1.) in the office area . 2.) throughout the main shop area. |
| 07/27/2006 | INSP - FULL | DRAMIREZ | Approved |