Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case: T06FR02272

Parcel: 127090150


Addresses:

122 N CRAYCROFT RD

Inspection Status: Violation

Inspection History: INSP - FULL

Date Description Inspector Results Comments
07/21/2006 INSP - FULL Violation 1). Currently no fire alarm exists in building 8, this is an E type occupancy and fire alarm is required before occupation. Please contact Capt. Ron Summers at 791-4502 for further info.
IFC 903.2.2 (modified locally) which states;
Section 903.2.2 Group E. An automatic fire sprinkler system shall be provided throughout all Group E Occupancies.
Exception: One story buildings when each room used for instruction has at least one exit door directly to the outside at ground level, and when rooms used for assembly purposes have at least one-half of the required exits directly to the exterior ground level, an automatic sprinkler system need not be provided.
2). Repair all electrical in classroom 8. IFC 605.1
3). Existing fire alarm in building 6-7-8 shall be tested or accepted by TFD. IFC 901.6
4). Currently smoke detectors (2) in classrooms 6-7-8- are above ceiling fans,. These smoke detectors shall be moved. IFC 901.6
5). Repair door closure in room 6-7-8. IFC 703.2.2