Case: T06FR02272
Case Details
Entered Date:
07/21/2006
Applicant:
RINCON CONGREGATIONAL CHURCH
Description:
inspection
Outstanding Inspections
Case Number: T06FR02272
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2006 | INSP - FULL | EGRIFFIN | Violation | 1). Currently no fire alarm exists in building 8, this is an E type occupancy and fire alarm is required before occupation. Please contact Capt. Ron Summers at 791-4502 for further info. IFC 903.2.2 (modified locally) which states; Section 903.2.2 Group E. An automatic fire sprinkler system shall be provided throughout all Group E Occupancies. Exception: One story buildings when each room used for instruction has at least one exit door directly to the outside at ground level, and when rooms used for assembly purposes have at least one-half of the required exits directly to the exterior ground level, an automatic sprinkler system need not be provided. 2). Repair all electrical in classroom 8. IFC 605.1 3). Existing fire alarm in building 6-7-8 shall be tested or accepted by TFD. IFC 901.6 4). Currently smoke detectors (2) in classrooms 6-7-8- are above ceiling fans,. These smoke detectors shall be moved. IFC 901.6 5). Repair door closure in room 6-7-8. IFC 703.2.2 |