Case: T06FR02250

Parcel: 13327001C


Addresses:

7980 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: INSP - AST/UST

Case Number - T06FR02250

Inspection Description - INSP - AST/UST

Inspection Status - Approved

Date Description Inspector Results Comments
09/12/2006 INSP - AST/UST Approved Final done and contractor will send me copy of electrical final. Verified electrical inspection with R.Hollander, issue with compressor needs to be rectified but the rest of the station is OK.
08/08/2006 INSP - AST/UST Approved Secondary piping inspection @ 5 psi. Advised that he will need electrical final prior to fire final.
08/03/2006 INSP - AST/UST Approved Primary piping inspection @ 50 psi, vapor recovery @ 5 psi for 2 hrs. OK to start on secondary piping.
07/18/2006 INSP - AST/UST Approved Passed tank tightness pre-burial test, held pressure for 2 hours @ 3 psi.