Inspection Status: Correction Required
Inspection History: VIOL - FLAMMABLE FINISHES
| Date |
Description |
Inspector |
Results |
Comments |
| 07/05/2006 |
VIOL - FLAMMABLE FINISHES |
|
Correction Required |
1503.2.6 No Smoking signs shall be posted conspicuously around spray booth. |
| 07/05/2006 |
VIOL - FLAMMABLE FINISHES |
|
Correction Required |
1504.1.2.5 A clear space shall be maintained around the spray booth not less than 3 feet in width. This space shall be kept free of any storage. |
| 07/05/2006 |
VIOL - FLAMMABLE FINISHES |
|
Correction Required |
1504.3 Filters shall be maintained in place and changed when necessary. |
| 07/05/2006 |
VIOL - FLAMMABLE FINISHES |
|
Correction Required |
1504.6.4 A portable fire extinguisher shall be provided not less than 30 feet from the paint booth. The extinguisher shall be rated at least 4A:40BC |
| 07/05/2006 |
VIOL - FLAMMABLE FINISHES |
|
Correction Required |
1503.4.3 An approved metal waste can equipped with a self-clossing lid shall be provided to contain rags and waste that is impregnated with finishing material. Contents of waste can shall be disposed of at least once daily. |