Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case: T06FR02151

Parcel: 11704141A


Addresses:

601 N STONE AV

Inspection Status: Correction Required

Inspection History: VIOL - FLAMMABLE FINISHES

Date Description Inspector Results Comments
07/05/2006 VIOL - FLAMMABLE FINISHES Correction Required 1503.2.6 No Smoking signs shall be posted conspicuously around spray booth.
07/05/2006 VIOL - FLAMMABLE FINISHES Correction Required 1504.1.2.5 A clear space shall be maintained around the spray booth not less than 3 feet in width. This space shall be kept free of any storage.
07/05/2006 VIOL - FLAMMABLE FINISHES Correction Required 1504.3 Filters shall be maintained in place and changed when necessary.
07/05/2006 VIOL - FLAMMABLE FINISHES Correction Required 1504.6.4 A portable fire extinguisher shall be provided not less than 30 feet from the paint booth. The extinguisher shall be rated at least 4A:40BC
07/05/2006 VIOL - FLAMMABLE FINISHES Correction Required 1503.4.3 An approved metal waste can equipped with a self-clossing lid shall be provided to contain rags and waste that is impregnated with finishing material. Contents of waste can shall be disposed of at least once daily.