Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

07/05/2006

Applicant:

ARIZONA AUTO BOUTIQUE INC

Description:

Full Inspection

Outstanding Inspections

Case Number: T06FR02151
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 11
End Date Description Inspector Results Comments
07/05/2006 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 304.1 Combustible waste shall not be allowed to accumulate within the spray booth.
07/05/2006 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.1 The electrical conduit located on the south side of the paint booth shall be repaired or replaced where wiring is exposed.
07/05/2006 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 The junction box located on the south side of the paint booth shall have an approved cover.
07/05/2006 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 The switch box located at the outside northwest corner of the spray booth shall have an approved cover.
07/05/2006 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 1503.2.6 No Smoking signs shall be posted conspicuously around spray booth.
07/05/2006 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 1503.4.3 An approved metal waste can equipped with a self-clossing lid shall be provided to contain rags and waste that is impregnated with finishing material. Contents of waste can shall be disposed of at least once daily.
07/05/2006 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 1504.1.2.5 A clear space shall be maintained around the spray booth not less than 3 feet in width. This space shall be kept free of any storage.
07/05/2006 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 1504.3 Filters shall be maintained in place and changed when necessary.
07/05/2006 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 1504.6.4 A portable fire extinguisher shall be provided not less than 30 feet from the paint booth. The extinguisher shall be rated at least 4A:40BC
07/05/2006 VIOL - HAZARDOUS MATERIALS,GEN TKNAPP Correction Required 2703.4 Material Safety Data Sheets shall be readily available on the premises for all hazardous materials.
07/05/2006 VIOL - HAZARDOUS MATERIALS,GEN TKNAPP Correction Required 2703.5 An NFPA 704 hazard identification sign shall be provided for the entrance to the paint booth.

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR02151
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/18/2006 INSP - FULL TKNAPP Approved