Case: T06FR02151
Case Details
Entered Date:
07/05/2006
Applicant:
ARIZONA AUTO BOUTIQUE INC
Description:
Full Inspection
Outstanding Inspections
Case Number: T06FR02151
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 11
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/05/2006 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 304.1 Combustible waste shall not be allowed to accumulate within the spray booth. |
| 07/05/2006 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 The electrical conduit located on the south side of the paint booth shall be repaired or replaced where wiring is exposed. |
| 07/05/2006 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The junction box located on the south side of the paint booth shall have an approved cover. |
| 07/05/2006 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The switch box located at the outside northwest corner of the spray booth shall have an approved cover. |
| 07/05/2006 | VIOL - FLAMMABLE FINISHES | TKNAPP | Correction Required | 1503.2.6 No Smoking signs shall be posted conspicuously around spray booth. |
| 07/05/2006 | VIOL - FLAMMABLE FINISHES | TKNAPP | Correction Required | 1503.4.3 An approved metal waste can equipped with a self-clossing lid shall be provided to contain rags and waste that is impregnated with finishing material. Contents of waste can shall be disposed of at least once daily. |
| 07/05/2006 | VIOL - FLAMMABLE FINISHES | TKNAPP | Correction Required | 1504.1.2.5 A clear space shall be maintained around the spray booth not less than 3 feet in width. This space shall be kept free of any storage. |
| 07/05/2006 | VIOL - FLAMMABLE FINISHES | TKNAPP | Correction Required | 1504.3 Filters shall be maintained in place and changed when necessary. |
| 07/05/2006 | VIOL - FLAMMABLE FINISHES | TKNAPP | Correction Required | 1504.6.4 A portable fire extinguisher shall be provided not less than 30 feet from the paint booth. The extinguisher shall be rated at least 4A:40BC |
| 07/05/2006 | VIOL - HAZARDOUS MATERIALS,GEN | TKNAPP | Correction Required | 2703.4 Material Safety Data Sheets shall be readily available on the premises for all hazardous materials. |
| 07/05/2006 | VIOL - HAZARDOUS MATERIALS,GEN | TKNAPP | Correction Required | 2703.5 An NFPA 704 hazard identification sign shall be provided for the entrance to the paint booth. |
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR02151
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/18/2006 | INSP - FULL | TKNAPP | Approved |