Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/03/2006 | VIOL - BUILDING SVCS & SYSTEMS | Approved | TFC 605.5 Extension cords shall not be a substitute for permenant wiwing. Cords shall not be extended through walls, ceilings, floors or under floors. Cords shall be used for only portable appliances. Misuse of cords in the following: 1.) under desk in the by regester. 2.) in the medical lab: a.) through the ceiling by counter. b.) through the ceiling behind door. 3.) in the medical billings classroom. 4.) over copy machine in hallway. |
|
| 07/03/2006 | VIOL - BUILDING SVCS & SYSTEMS | Approved | TFC605.4.2 Receptacle power taps shall be directly connected to a permanently installed receptacle. The use of power taps connected togrther in a piggy-back manner to accommodate multiple appliances shall be discontinued. |
|
| 07/03/2006 | VIOL - BUILDING SVCS & SYSTEMS | Approved | TFC 605-1 any computer connected in series as are the computers located in " Medical Billing " classroom shall be powered by a permenantly installed receptacle. Any electrical modification shall be installed in accordance to the I.E.C. ( INTERNATIONAL ELECTRICAL CODE ). |
|
| 07/03/2006 | VIOL - BUILDING SVCS & SYSTEMS | Approved | TFC 605.6 Approved cover boxes shall be provided for all switch and electrical outlet boxes. 1.) behind copy machine locateded in hallway. 2.) in physical therapy rooms, #1 and #2. |