Description:

full inspection

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR02147
Case Description: INSPECTION
Total Completed Inspections - 13
End Date Description Inspector Results Comments
07/03/2006 VIOL - PRECAUTION AGAINST FIRE DRAMIREZ Approved TFC 305.2 Clearance of combustable material from heat producing devices shall be maintained. Accumulation of lint behind dryer may present a hazard. The missing flex hose to dryer shall be replaced.
07/03/2006 VIOL - FIRE RESIST.RATED CONST DRAMIREZ Approved TFC 703.1 Fire-resistance rated material shall be maintained. Ceiling tile in " VET LAB " shall be repaired
07/03/2006 VIOL - MEANS OF EGRESS DRAMIREZ Approved TFC 1008.1.8.3 Locks and latches shall be permitted in classrooms with exit doors leading to the parking lot, provided a sign is posted above door stating, " THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED ).
07/03/2006 VIOL - FIRE SERVICE FEATURES DRAMIREZ Approved TFC 504.2 Exterior doors that have been renderd non-functional and retain a functinal door exterior appearance shall have a sign affixed to the exterior side of the door the words, " THIS DOOR BLOCKED ), min. of 6 inch high letters. 1.) four exterior doors on the north wall of the building. 2.) 3 doors located next to main power shutoff panel. 3.) rear of building, next to transformers,
07/03/2006 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved TFC 605.6 Approved cover boxes shall be provided for all switch and electrical outlet boxes. 1.) behind copy machine locateded in hallway. 2.) in physical therapy rooms, #1 and #2.
07/03/2006 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved TFC 605-1 any computer connected in series as are the computers located in " Medical Billing " classroom shall be powered by a permenantly installed receptacle. Any electrical modification shall be installed in accordance to the I.E.C. ( INTERNATIONAL ELECTRICAL CODE ).
07/03/2006 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved TFC605.4.2 Receptacle power taps shall be directly connected to a permanently installed receptacle. The use of power taps connected togrther in a piggy-back manner to accommodate multiple appliances shall be discontinued.
07/03/2006 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved TFC 605.5 Extension cords shall not be a substitute for permenant wiwing. Cords shall not be extended through walls, ceilings, floors or under floors. Cords shall be used for only portable appliances. Misuse of cords in the following: 1.) under desk in the by regester. 2.) in the medical lab: a.) through the ceiling by counter. b.) through the ceiling behind door. 3.) in the medical billings classroom. 4.) over copy machine in hallway.
07/03/2006 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Approved TFC 906.2 Portable fire extinguishers shall be maintained and serviced annually. There is a count of 12 extinguishers that need servicing.
07/03/2006 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Approved TFC 901.6.1. Fire Department Connecions are damaged and shall be repaired in accordance to TFC 901.6
07/03/2006 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Approved TFC 901.6.2 Maintenance records for sprinkler systems shall be available on the premises at all times.
07/03/2006 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Approved TFC 906.1 Sprinkler system is past due for inspection.
07/03/2006 INSP - FULL DRAMIREZ Approved