Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T06FR00660

Parcel: 117041900


Addresses:

127 W 5TH ST


Inspection Status: Approved

Inspection History: VIOL - LUMBER YARD & WOOD FAC.

Case Number - T06FR00660

Inspection Description - VIOL - LUMBER YARD & WOOD FAC.

Inspection Status - Approved

Date Description Inspector Results Comments
05/10/2006 VIOL - LUMBER YARD & WOOD FAC. Approved
04/04/2006 VIOL - LUMBER YARD & WOOD FAC. Violation Buildup of saw dust:
TFC 1903.2 Dust control. Equipment or machinery located inside
buildings which generates or emits combustible dust shall be
provided with an approved dust collection and exhaust system
installed in accordance with Chapter 13 and the International
Mechanical Code. Equipment or systems that are used to collect,
process or convey combustible dusts shall be provided
with an approved explosion control system.
***install an approved system for the type work being performed in the building.
04/04/2006 VIOL - LUMBER YARD & WOOD FAC. Violation Electrical hazards:
TFC 1903.4 Electrical equipment. Electrical wiring and equipment
shall comply with the ICC Electrical Code.
***Upgrade the electrical in its entirety, to meet the above standards.
04/04/2006 VIOL - LUMBER YARD & WOOD FAC. Violation General housekeeping-sawdust, clutter:
TFC 1903.3.1 Housekeeping. Provisions shall be made for a systematic
and thorough cleaning of the entire plant at sufficient
intervals to prevent the accumulations of combustible
dust and spilled combustible or flammable liquids.
***Clean and continue to keep clean the working area.