Case: T06FR00539

Parcel: 12705071A


Addresses:

4750 E SPEEDWAY BL

Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
03/29/2006 VIOL - BUILDING SVCS & SYSTEMS Violation Open electrical box in waiting room:
TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited.
***Approved covers shall be provided for all switch and electrical outlet boxes.
03/29/2006 VIOL - BUILDING SVCS & SYSTEMS Violation Extension cord use:
TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring.
*** Replace with approved power strip.
03/29/2006 VIOL - BUILDING SVCS & SYSTEMS Violation Main breaker box-multiple problems:
TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated.
*** DSD Electrical inspector shall be referred, to inspect the condition of electrical service. [check grounding, routing, installation, etc.]