Case: T06FR00539
Case Details
Entered Date:
03/29/2006
Applicant:
HULLINGER ROBERT D & LISA GAIL CP/RS
Description:
Full inspection done 3/28/06.
Outstanding Inspections
Case Number: T06FR00539
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/29/2006 | VIOL - BUILDING SVCS & SYSTEMS | BCOBB | Violation | Extension cord use: TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. *** Replace with approved power strip. |
| 03/29/2006 | VIOL - BUILDING SVCS & SYSTEMS | BCOBB | Violation | Main breaker box-multiple problems: TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. *** DSD Electrical inspector shall be referred, to inspect the condition of electrical service. [check grounding, routing, installation, etc.] |
| 03/29/2006 | VIOL - BUILDING SVCS & SYSTEMS | BCOBB | Violation | Open electrical box in waiting room: TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. ***Approved covers shall be provided for all switch and electrical outlet boxes. |
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR00539
Case Description: INSPECTION
Total Completed Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/21/2006 | VIOL - FIRE PROTECTION SYSTEMS | BCOBB | Approved | |
| 11/21/2006 | INSP - FULL | BCOBB | Approved | |
| 11/21/2006 | INSP - REINSPECTION | BCOBB | Approved | Fire issues abated, except Electrical. City Electrical inspectors wrote 5 violations and will conduct follow up. |