Permit: T06EL01930

Parcel: 111060090

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/22/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/17/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BURY G.E.C/BOND CONDUCTOR MINIMUM 12" OR SECURE TO STRUCTURE.
2. LABEL PANEL DIRECTORY.
3. FEEDER CONDUCTORS NOT ALLOWED IN SAME GUTTER AS SERVICE CONDUCTORS.
4. BRANCH CKT CONDUCTORS NOT ALLOWED IN SAME GUTTER EITHER.
5. HAVE GUTTER OPEN FOR INSPECTION.
6. J-BOXES ARE OVERFILLED, UNGROUNDED AND NEED PROPER CONNECTOR FOR CABLES.
7. WHAT ARE PANEL VOLTAGES? 120/240 OR 120 ONLY?
CHECK FEEDER WIRING - PROVIDE INTERIOR ACCESS.
11/03/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*