Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/22/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/17/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BURY G.E.C/BOND CONDUCTOR MINIMUM 12" OR SECURE TO STRUCTURE. 2. LABEL PANEL DIRECTORY. 3. FEEDER CONDUCTORS NOT ALLOWED IN SAME GUTTER AS SERVICE CONDUCTORS. 4. BRANCH CKT CONDUCTORS NOT ALLOWED IN SAME GUTTER EITHER. 5. HAVE GUTTER OPEN FOR INSPECTION. 6. J-BOXES ARE OVERFILLED, UNGROUNDED AND NEED PROPER CONNECTOR FOR CABLES. 7. WHAT ARE PANEL VOLTAGES? 120/240 OR 120 ONLY? CHECK FEEDER WIRING - PROVIDE INTERIOR ACCESS. |
|
| 11/03/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |