Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/28/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/03/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. PARTIAL ROUGH IN SHED - COMPLETE DRYWALL, INSTALL COVER PLATES. INSTALL ROMEX CONNECTOR FOR 2 GANG SW BOX 2. OK U.G |
|
| 12/21/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SUPPORT 3/4" EMT WITHIN 3' OF PANEL OUTSIDE AT SERVICE. 2. TYPE NM CABLE NOT APPROVED FOR UNDEGROUND USE 3. SPLICES MUST BE IN APPROVED J-BOX 4. MIN. CONDUIT DEPTH 18" BELOW GRADE FOR PVC 5. NAIL PLATES REQUIRED TO PROTECT CABLES PASSING THROUGH 1 1/2" STUDS. INSTALL BUSHINGS CORRECTLY. 6. USE ROMEX CONNECTORS FOR METAL BOX. |