Permit: T06EL01798

Parcel: 138061290


Addresses:

859 W SANTA ROSA ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/28/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/03/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. PARTIAL ROUGH IN SHED - COMPLETE
DRYWALL, INSTALL COVER PLATES.
INSTALL ROMEX CONNECTOR FOR 2 GANG SW BOX
2. OK U.G
12/21/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SUPPORT 3/4" EMT WITHIN 3' OF PANEL OUTSIDE AT SERVICE.
2. TYPE NM CABLE NOT APPROVED FOR UNDEGROUND USE
3. SPLICES MUST BE IN APPROVED J-BOX
4. MIN. CONDUIT DEPTH 18" BELOW GRADE FOR PVC
5. NAIL PLATES REQUIRED TO PROTECT CABLES PASSING THROUGH 1 1/2" STUDS. INSTALL BUSHINGS CORRECTLY.
6. USE ROMEX CONNECTORS FOR METAL BOX.