Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/04/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEAL OPEN KNOCKOUTS IN PANEL 2) EQUIPMENT GROUND BAR CANNOT BE CONNECTED USING SHEET METAL SCREWS 3) INSTALL BREAKERS LISTED FOR USE IN SQUARE D PANEL 4) EXPOSED PVC TO BE SCHEDULE 80 5) ROMEX CABLE CANNOT BE INSTALLED IN UNDEGROUND RACEWAY THIS IS WET LOCATION 6) STRAP PVC WITHIN 3' OF CONNECTIONS TO PANEL 7) INSTALL GASKET ON LB COVER 8) WHITE CONDUCTORS USED AS PHASE CONDUCTORS TO BE RE-IDENTIFIED 9) NEED PANEL DIRECTORY 10) OPEN JUNCTION BOX FOR INSPECTION 11) VERIFY PERMIT FOR NEW A/C UNIT. PROVIDE COPY 12) INSTALL LOCK NUTS ON CONNECTORS 13) RESCHEDULE WHEN READY |