Permit: T06EL01104

Parcel: 110090270

Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
07/11/2006 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
1. POST ADDRESS OUTSIDE OF STRUCTURE
2. A PERMANENT ADDRESS LABEL IS NEEDED
3. INSTALL A GROUNDING ELECTRODE SYSTEM
4. GAS AND WATER WILL NEED TO BE BONDED
5. PVC LB TO USE A FITTING TO ATTACH TO PANEL
6. SUPPORT CONDUITS & RISER BELOW PANEL
7. MAINTAIN WORKING CLEARANCE IN FRONT OF SERVICE 3'
8. USE APPROVED ELECTRICAL SUPPORT STRAPS.
9. NO MORE THAN 360 DEGREE IN A CONDUIT RUN. A POLL BOX MAY BE NEEDED.
10. CONDUCTOR TO BE LISTED FOR DIRECT BURIAL.