Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/11/2006 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* 1. POST ADDRESS OUTSIDE OF STRUCTURE 2. A PERMANENT ADDRESS LABEL IS NEEDED 3. INSTALL A GROUNDING ELECTRODE SYSTEM 4. GAS AND WATER WILL NEED TO BE BONDED 5. PVC LB TO USE A FITTING TO ATTACH TO PANEL 6. SUPPORT CONDUITS & RISER BELOW PANEL 7. MAINTAIN WORKING CLEARANCE IN FRONT OF SERVICE 3' 8. USE APPROVED ELECTRICAL SUPPORT STRAPS. 9. NO MORE THAN 360 DEGREE IN A CONDUIT RUN. A POLL BOX MAY BE NEEDED. 10. CONDUCTOR TO BE LISTED FOR DIRECT BURIAL. |