Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/03/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* SPOKE WITH DAN ABOUT PROJECT |
|
| 09/21/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLEASE VERIFY PERMITS FOR NEW WIRING TO INTERIOR WIRE MOLD 2. M/C ABLE TO TERMINATE WITH APPROVED FITTINGS. 3. BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE APPROVED EXTENDER RINGS 314.20 4. IF NEW WIRING IN KITCHEN PLEASE VERIFY 2 CIRCUITS SERVING COUNTER TOP. 5. WHAT IS PVC CONDUIT RUNNING THROUGH CLOSET 6. WE HAVE GROUNDED RECEPTACLES ON UNGROUNDED SYSTEM. 7. PLEASE VERIFY PERMIT FOR NEW WATER HEATER. 8. USE APPROVED FITTINGS WITH PVC BOXES. 9. PLEASE COMPLETE OLD SERVICE UPGRADE PERMIT. |