Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06EL01017
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/30/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
09/12/2006 | ELECTRIC - FINAL | Partial Approval | FINISH #2 OF PREVIOUS INSPECTIONS LISTING IS TO BE FOR CABINET AS THE PAPERWORK SHOWS. | |
09/08/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH PREVIOUS ITEMS #2 & #8 OK SEALS |
|
09/06/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SEPARATE CONDUCTORS WITH PACKING 2. VERIFY LISTING FOR AIR/WATER PUMP 3. TIGHTEN LOOSE FITTINGS 4. WE HAVE MULTIPLE TERMINATIONS AT LUGS 5. SHEETMETAL SCREW NOT ALLOWED FOR GROUNDING 6. USE APPROVED PARTS FOR NEUTRAL CONNECTIONS 7. FILL UNUSED OPENING IN GUTTER 8. SEPARATE DATA FROM VOLTAGE CIRCUITS 9. VERIFY DISCONNECTION OF ALL POWER 514.13 10. CORRECTLY LABEL PANEL DIRECTORIES 11. INSTALL BREAKERS FOR PHASE LOADS PER PLANS' 12. AIR/WATER PUMP ON PLANS 220V NOT 120V |