Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/22/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. LABEL SERVICE DISCONNECT PER NEC 230.70 2. NEED PANEL DIRECTORY PER NEC 408.4 3. INSTALL BUSHING AROUND CABLES THROUGH 2" KNOCKOUT BACK OF PANEL. 4. INSTALL BREAKERS LISTED FOR USE IN PANEL - NEC 110.3 5. REIDENTIFY WHITE WIRE USED AS PHASE CONDUCTOR FOR SPA. 6. INSTALL 2 GROUND RODS MIN. 6' APART - NEC 250 7. NEED TO BOND GAS & WATER PIPING - NEC 250 8. BOND OFFSET NIPPLE & SERVICE RISER PER NEC 250.92 9. CANNOT SEE INTO METER ENCLOSURE SERVICE ENERGIZED PRIOR TO APPROVALS. 10. PANEL DOOR DOES NOT CLOSE PROPERLY |