Permit: T06EL00134

Parcel: 120074140


Addresses:

308 W AVIATION DR


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06EL00134

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/16/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/15/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SEE NOTES -- DO NOT CALL FOR INSP. UNTIL WORK DONE CORRECTLY USE QUALIFIED ELECTRICIAN
02/14/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*WHAT HAPPENED TO THE GROUND WIRES?
THEY WHERE TWISTED TOGETHER IN THE J-BOX SEE NOTES LAST INSPECTION
02/08/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*INSTALL BUSHING OR CLAMPS TO PROTECT WIRING ( ROMEX)
ENTERING J-BOX IN PORCH.
USE WIRE NUT O CONNECT GROUND WIRE TOGETHER.
GROUND J-BOX & LABEL ( J-BOX)
01/27/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CHANGE TO SERVICE UPGRADE PERMIT-NEW SERVICE
2) EXPOSE GROUND RODS-2 REQUIRED 6' MINIMUM APART
3) #14 WIRE TO BE ON 15 AMP BREAKERS
4) ID THE NEUTRAL WIRE WHITE
5) EXPOSED ROMEX IN PORCH SHOULD BE IN RACEWAY