Addresses:

2201 N COLUMBUS BL

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
12/12/2006 INSP - INITIAL CODE ENFORCMENT Approved KITCHEN - ELECTRICAL OUTLET EAST WALL SHOWS OPEN GROUND. DOOR DOES NOT SEAL PROPERLY AND HAS LARGE GAPS.
WASHER AREA - LIGHT FIXTURE HAS NO GLOBE AND IS RIGHT UP AGAINST SHELVING, LESS THEN 18". VENT LINE AND DRAIN POSSIBLY INSTALLED WITHOUT PERMITS. DRYER VENT CONNECTED TO WHAT APPEARS TO BE THE ORIGINAL WATER HEATER VENT PIPE. AREA BEHIND WASHER/DRYER IS FULL OF LINT AND REQUIRES CLEANING.
DINING ROOM - WINDOW CRANK INOP. DOOR DOES NOT SEAL PROPERLY AND DOOR FRAME IS DETERIORATED AND CRACKED.
LIVING ROOM - DOOR DOES NOT SEAL PROPERLY. LACKS WINDOW CRANKS. ELECTRICAL OUTLET ON THE SOUTH WALL SHOWS OPEN GROUND. MANY REPAIRS TO THE CEILING DUE TO ROOF DAMAGE.
HALLWAY CARPET IS UNSECURED AND POSES A TRIP HAZARD. EMERGENCY LIGHT IN HALLWAY IS INOP.
BEDROOM 1 - LIGHT FIXTURE IN THE CLOSET LACKS PROPER CLEARANCE AND GLOBE. EXTENSION CORD CONNECTED TO FIXTURE TO POWER TV. LACKS WINDOW CRANK, WINDOW INOP.
MAIN BATHROOM - LACKS TUB FAUCET FIXTURES. SINK MIRROR IS BROKEN, LACKS TOILET FLUSH HANDLE.
BEDROOM 2 - BEDROOM AND CLOSET DOOR ARE NOT ATTACHED TO THE DOOR FRAMES. CLOSET LIGHT LACKS PROPER CLEARANCE AND GLOBE. ACCESS TO THE WINDOW IS BLOCKED BY DEBRIS.
BEDROOM 3 - WINDOW CRANKS INOP. CLOSET LIGHT LACKS GLOBE AND PULL CHAIN IS INOP.
BEDROOM 4 - WINDOW ACCESS BLOCK BY CLOTHES DRESSER.
OUTSIDE REAR STRUCTURE - WOOD IS SEVERLY DETERIORATED AND LACKS SUFFICIENT WEATHER PROTECTION. LIGHT FIXTURE AT REAR DOOR LACKS GLOBE.
MAIN ELECTRICAL SERVICE - MISSING BLANKS AND PLUGS, LACKS LABELING AND ADDRESSING. DUE TO RUST AND DETERIATION UNABLE TO PULL DEAD FRONT.
WATER LINES ON THE WEST AND NORTH SIDE OF THE STRUCTURE LACK PROPER WEATHER PROTECTION.
WATER HEATER LACKS COLD WATER SHUT OFF. TPRV IS NOT ACCESSIBLE. VENT PIPE IS BELOW ROOF LINE. ALSO LACKS PROPER ENCLOSURE.
ADDITION OF PORCH AND CARPORT ( ONE PEICE ) ON THE NORTH AND WEST SIDE OF THE STRUCTURE IS ATTACHED. BEAM IS INSTALLED INCORRECTLY AND COVER (ROOF) HAS BEEN PARTIALLY REMOVED.
FRONT PORCH IS SEPERATING FROM THE ROOF TRUSSES. APPROX 3 INCH GAP AT THE NORTH EAST CORNER.
ROOF ON THE SOUTH SIDE OF THE DWELLING SHOWS SEVERE DETERIORATION. ROOF PROTECTION IS PEELED AND TRUSSES ARE BOWED AND SAGGING. RM