Case: T06DV00195

Parcel: 123021150


Addresses:

2132 N FORGEUS AV

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
04/10/2006 INSP - INITIAL CODE ENFORCMENT Approved MADE INSPECTION OF THE SERVICE EQUIPMENT WHICH INCLUDE SEVERAL BUILDINGS GROUPED IN A POD.
EACH BUILDING HAS TWO OR THREE UNITS WITH THE SERVICE EQUIPMENT TO EACH OF THESE BUILDINGS GROUPED AT A CENTRAL LOCATION.
WHAT WAS NOTED IS THAT THE SERVICE EQUIPMENT BEING DILAPIDATED AND NOT USEABLE, HANDLE BROKEN, RUSTED ENCLOSURES, MISUSE OF COLOR CODE, IMPROPER WIRE TERMINATIONS, IMPROPER SWITCH HEIGHTS, MULTIPLE LUGGING, GROUNDING SYSTEM NOT INSTALLED.