Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case Details

Status:

REFERRED

Type:

COMMERCIAL ZONING

Entered Date:

03/07/2006

Applicant:

MEEKER FAMILY TR & HARRIS FAMILY TR

Description:

ELECTRICAL SERVICE EQUIPMENT.

Outstanding Inspections

Case Number: T06DV00195
Case Status: REFERRED
Case Description: COMMERCIAL ZONING
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
EMERGENCY CALL OUT None Not Inspected

Completed Inspections

Case Status: REFERRED
Case Number: T06DV00195
Case Description: COMMERCIAL ZONING
Total Completed Inspections - 2
End Date Description Inspector Results Comments
02/21/2006 INSP - FOLLOW UP CODE ENFORCE JORTA Approved
04/10/2006 INSP - INITIAL CODE ENFORCMENT JORTA Approved MADE INSPECTION OF THE SERVICE EQUIPMENT WHICH INCLUDE SEVERAL BUILDINGS GROUPED IN A POD. EACH BUILDING HAS TWO OR THREE UNITS WITH THE SERVICE EQUIPMENT TO EACH OF THESE BUILDINGS GROUPED AT A CENTRAL LOCATION. WHAT WAS NOTED IS THAT THE SERVICE EQUIPMENT BEING DILAPIDATED AND NOT USEABLE, HANDLE BROKEN, RUSTED ENCLOSURES, MISUSE OF COLOR CODE, IMPROPER WIRE TERMINATIONS, IMPROPER SWITCH HEIGHTS, MULTIPLE LUGGING, GROUNDING SYSTEM NOT INSTALLED.

Completed Activity Special Conditions

Case Description - COMMERCIAL ZONING
Case Number - T06DV00195
Case Status: REFERRED
Total Completed Case Activity Conditions: 3
Date Name
04/24/2006 CONTACTED BY PHONE
03/30/2006 NOTICE OF VIOLATION ISSUED
10/31/2006 VIOLATION CLOSED

Documents

File Name Document Type  
N.O.V. WITH SECTION NUMBERS.PDF DOCUMENTS VIEW
2006-02-17 001 DISCONNECT WITHOUT INTERNAL INSULAT IMAGES VIEW
2006-02-17 002 INTERNAL VIEW OF DISCONNECT NO INSU IMAGES VIEW
2006-02-17 003 MODIFICATIONS WITHOUT PERMITS.JPG IMAGES VIEW
2006-02-17 004 OVERALL VIEW OF SERVICE .JPG IMAGES VIEW
2006-02-17 011 VIEW OF MAIN DISCONNECT .JPG IMAGES VIEW
2006-02-17 012 MULTIPLE CONDUCTORS UNDER ONE LUG . IMAGES VIEW
2006-02-17 013 WIRE CREEPING DUE TO LOOSE CONNECTI IMAGES VIEW
2006-02-17 014 WIRE CREEPING TO OVER HALF OF THE L IMAGES VIEW
2006-02-17 015 GUTTER CONDUCTORS .JPG IMAGES VIEW
2006-02-17 016 IMPROPER REPAIRS OPEN KNOCKOUTS .JP IMAGES VIEW
2006-02-17 017 OPEN KNOCKOUTS .JPG IMAGES VIEW
2006-02-17 018 REPLACEMENT DISCONNECT WITH OUT PER IMAGES VIEW
2006-02-17 019 TYPICAL ORIGINASL DISCONNECT .JPG IMAGES VIEW
2006-02-17 021 OTHER REPAIRS 30 AMP ON NO.12 .JPG IMAGES VIEW
2006-02-17 022 ORIGINAL TYPE DISCONNECT .JPG IMAGES VIEW
2006-02-17 023 ORIGINAL DISCONNECT .JPG IMAGES VIEW
2006-02-17 036 LOCKED OUT DANGEROUS DISCONNECT .JP IMAGES VIEW