Permit: T06CM06548

Parcel: 13826318F

Inspection Status: Denied

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
10/11/2007 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. APPROVED PLANS CALL FOR NEUTRAL CONDUCTOR TO BE INSTALLED AT SERVICE EQUIP. SEE SHEET 19
2. NEC REQUIRES NEUTRAL PER 250.4 A-5, 250.24 B
3. PROVIDE LETTER OF TORQUE FOR SERVICE EQUIP.