Permit: T06CM06423

Parcel: 13320129C


Addresses:

6300 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/24/2008 MECHANICAL - FINAL Approved
10/23/2008 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
10/21/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. PROVIDE SCREENS IN ALL EXHAUST T-TOPS
2. PACKAGE UNITS ON ROOF NOT FUSED CORRECTLY
3. PAINT ALL EXPOSED PVC VENTS ON ROOF
4. PROVIDE AIR BALANCE REPORT
5. ALL FIRE DAMPERS AND DUCT DETECTORS HAVE BEEN TESTED
10/20/2008 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
10/16/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. REPAIR ALL REFER LINE INSULATION ON ROOF
2. SEAMS ARE NOT STICKING TOGETHER
3. REPAIR DAMAGED T-TOPS
4. EXPOSE ALL MECHANICAL WORK IN ALL COMMON AREAS
FOR INSPECTION
10/15/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
OK FOR FINAL C BLDG.
TESTED FIRE DAMPERS & DUCT SMOKE DETECTORS
10/13/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
DAMPERS AT 1134/1234 NON-OP.
- DO NOT USE AN A/C UNIT TO CONNECT BRACING FOR FIREPLACE FLUE
10/08/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
OK FOR FINAL A BLDG. &
LIVING AREAS & CORRIDORS IN B BLDG.
10/07/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
TESTED INTERLOCK WITH KITCHEN EXHAUST & MAKE UP AIR
10/06/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
EXTEND FIREPLACE FLUE ON ROOF. PROVIDE GREASE CUPS UNDER FANS. SECURE FIREPLACE FLUES ON ROOF AND REPLACE DAMAGED CAP.
10/01/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
- FINISH ALL WORK ON ROOF BLDG. A
- CANVAS COVERS, GREASE DUCT CONNECTIONS, PAINT ON GREASE DUCTS AND PVC.
- LABEL DATA PLATES
- NEED TO TEST ALL UNITS WITH FIRE ALARM SYSTEM, ETC.
09/24/2008 MECHANICAL - FINAL Partial Approval OK FOR FINAL BLDG. C
1ST & 2ND FLOORS
09/23/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. BLDG. B UNITS OK FOR FINAL
2. BLDG. B CORRIDORS NEED TO BE COMPLETED
3. ALL DUCT SMOKE DETECTORS MUST BE CONNECTED TO FIRE ALARM SYSTEM.
09/22/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
3RD FLOOR BLDG. B UNITS OK FOR FINAL
08/19/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
OK FOR FINAL UNITS 1101 AND 1123 ONLY
08/18/2008 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
FAN COIL CIRCUIT BREAKERS NOT PROPER SIZE
SMALL CONDENSOR CIRCUIT BREAKER NOT PROPER SIZE
08/18/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*