Permit: T06CM06423

Parcel: 13320129C


Addresses:

6300 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/05/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
10/31/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
- PROVIDE AN APPROVED DRAIN AND SEAL CONN. AT FLOOR
AT ADA SHWRS
- PROVIDE SHWR HOSE FOR HW TEST
- COMPLETE PREVIOUSLY NOTED ITEMS AND FOUNTAIN/POOL PERMITS
10/28/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
BLD. D - 2ND LEVEL WATER OK
EMPLOYEE BREAK ROOM & RESTROOM AT LAUNDRY AREA OK
10/24/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
SEE NOTES FROM REGULAR INSPECTION DATED 10/24/08
1, 2, 6, 8, 10, 11, 12, 14

NEED COMPLETION OF VENT FOR LAUNDRY WATER HEATER, WITH DRIP PAN UNDER WATER HEATER.

DRAINS IN EMPLOYEE RESTROOM AT LAUNDRY FLUSH TO FINISH FLOOR

FLOOR CLEANOUTS TO BE FRANK PATTERN COVERS FOR TRAFFIC

BLD. D FIXTURES OK IN ROOMS

AFTER HRS. INSP. CHECK
TOTAL $150.00
2 CHECKS @ $75.00 EA. (CK. #'s 111500, 111501)
10/24/2008 PLUMBING - FINAL Not ready for Inspection JAMES @ 235-0180

1. JANITOR SINK CHEMICAL ADDITION GETS WATER FROM WHERE? THIS MAY REQUIRE A SOURCE OF WATER BESIDES THE FAUCET AT THIS SINK.
2. INSULATE WATER HEATER & BOILERS
3. PROVIDE SUPPORT EXPANSION TANK AT WATER HEATER
4. PROVIDE GRATE FOR FLOOR SINK IN LAUNDRY
5. SUPPORT WATER HEATER CONDENSATE DRAIN PIPING
6. SUPPORT GAS PIPING AT VALVE TO DRYER IN
NORTHEAST CORNER
7. COMPLETE EQUIPMENT INSTALLS IN LAUNDRY
8. INSTALL ACCESS PANEL IN EMPLOYEE ROOM RESTROOM
9. SECURE TEMPERING VALVE IN EMPLOYEE RESTROOM BY LAUNDRY
10. COMPLETE VENT PIPE IN SOFTENER ROOM
11. CPVC TO STEEL REQUIRES CPVC MALE I.P CONNECTION TO BRASS FEMALE I.P CONNECTION AT SOFTENER
12. SALT TANK REQUIRES APPROVED GRAVITY DRAIN TO RECEPTOR FOR OVERFLOW TANK DRAIN.
13. ALL ROOF DRAINS REQUIRE DEMOS
14. NEED ACCESS TO ROOMS WANTING TO OCCUPY
15. NEED TO SEE BLD. D JANITOR CLOSET
16. SECTION D ROOMS 1251, 1160, 1166 NEED INSPECTION
17. ALL HOSE BIBS REQUIRED INSTALL
18. TRASH ENCLOSURE INSPECTION
19. VERIFICATION OF HOT & COLD CONNECT AT ALL ROOMS.
10/23/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELED
10/22/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
D BLD. 2ND LEVEL ALL ROOM FIXTURES EXCEPT #1251 OK

1. EXPOSE CLEANOUTS FOR SHAMPOO SINKS IN SALON
10/20/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1ST LEVEL ROOMS BLD. D ALL OK EXCEPT 1160 & 1166
BLD. A

1. LAV FOR EMPLOYEES REQUIRES HOT TEMPERING
2. CHEMICAL ADDITIONS FOR MOP SINK REQUIRES A SEPARATE WATER SERVICE
3. CHEMICAL ADDITION TO DISHWASHER RINSE ADDITION MAY REQUIRE BACKFLOW ADDITION
10/17/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
2ND LEVEL BLD. D
ROOMS ONLY ALL EXCEPT 1251, 1254, 1255, 1256, 1257, 1261, 1274

RECEIVED CHLORINE & BACTERIA REPORT FOR POTABLE WATER
10/16/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
PLUMBER NEEDS TO COMPLETE ALL WORK IN EACH BUILDING TO DO FINAL INSPECTIONS. WE HAVE PROVIDED LISTS IN THE PAST, COMPLETE THEM AND HAVE ALL WORK COMPLETED OR YOU WILL PAY REINSPECTION FEES. LAST WARNING.
10/14/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
PLUMBER NEEDS TO CORRECT GAS REGULATOR VENT
PROVIDE SUPPORT FOR PVBS
PROVIDE NON-FERROUS PIPING UPSTREAM OF ASSEMBLY
PVB SHALL BE INSTALLED 12" ABOVE FLOOD LEVEL
PROVIDE CERTS. AFTER MAKING CORRECTIONS
SECURE HB VAC B
10/07/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
ALL BEV. EQUIPT. MUST BE INSTALLED FOR FINAL INSP.
(NOTE: ISOLATE ALL DFS AND BEV. EQUIPT. DURING DISINFECTION)

NEED TO SEE TEMPERING CONTROLS AT BOILER FOR TEMPERING REQUIRED AT PUBLIC LAVATORY. EXPOSE ACCESS TO CPVC CONN. AT BOILER.

EXPOSE CLEANOUTS COVERED OR MISSING
PROVIDE AG AT DISPOSER HOSE.
CORRECT DRIP AT 3 COMP SINK
RM. 250 CLIP SINK
10/03/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. 1ST FLOOR A PUBLIC TOILET RMS. OK
2. WALKED KITCHEN W/PLUMBER AND IDENTIFIED CORRECTIONS NEEDED.
3. NEED TO INSPECT BOILERS.
4. THEN REINSPECT FIXTURES ONCE HOT WATER SYSTEM IS ENERGIZED.

NOTE: BOILERS ALSO REQUIRE STATE BOILER
INSPECTOR CERT.
10/02/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
C BUILD 1ST FLOOR PRIVATE RMS. OK

NOTE: 2003 UPC REQUIRES DISINFECTION OF BUILDING WATER SUPPLY 609.9
10/01/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- LEVEL 2 BLD. C - PRIVATE RM. FIXTURES OK
- MS NOT YET INSTALLED
- PROVIDE ACCESS TO ALL CPVC THREADED CONNECTIONS AS REQUIRED BY UPC IS #20 AND PREVIOUSLY AGREED
- A BUILD NOT READY. JAMES.
09/29/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
09/26/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
- 2ND LEVEL SEC. C WEST TO EAST PRIVATE
ROOM FIXTURES OK

- HOSE BIBS MISSING VAC BREAKER
- CONSTRUCTION PERSONNEL IS USING WATER
- PLEASE CORRECT
- NOTE: STERILIZATION IS REQUIRED FOR POTABLE WATER
09/24/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
SEC. B FINAL FIXTURE INSP. IN ROOMS OK
WILL NEED TO VERIFY AIR GAP AT HANDHELD SHOWERS AND THE INSTALLATION OF ACCESS PANELS WHERE REQUIRED.
09/23/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1. L1 SEC B FIXTURES OK EXCEPT FOR
RMS. 1102, 1106 AND 1110
2. PROVIDE ADEQUATE ACCESS TO TRAP PRIMER VALVES
3. PLANS NEED TO BE IN AN AREA THAT IS NOT LOCKED DURING INSP. HOURS.
09/19/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
LEVEL 3 FIXTURES OK
LEVEL 2 BUILD. SEC B FIXTURES OK EXCEPT RMS. 1204 & 1223
09/15/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1317 LAVATORY NOT CORRECTED
ALL OTHER RMS. 3RD FLOOR B FIXTURES OK
I HAVE CIRCLED MANY UNCOMPLETED INSPECTION REQUESTS
PLEASE READ AND PROVIDE THE OUTSTANDING REQUIRED PLAN REVISIONS PREVIOUSLY REQUESTED. FAILURE TO COMPLY WILL RESULT IN REINSPECTION FEES.
09/12/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
09/11/2008 PLUMBING - FINAL Cancelled PER ZEE
09/09/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
08/28/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1317 CORRECT LAV P-TRAP (INSTALLED BACKWARDS)
1318 & 1319 LEAKS AT KS
1313 LEAK AT LAV 1310 KS TRAP ARM
TUB SPOUTS
08/26/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
08/19/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
FINAL FIXTURES RMS 1101 AND 1123 OK

PROVIDE DOCUMENTATION FOR COMPLIANCE OF
UPC SEC 609.9 FOR STERILIZATION OF BUILDING WATER SYSTEM
08/18/2008 PLUMBING - FINAL Not ready for Inspection UNIT #1124 CORRECT CONDENSATE DRAIN TO LAV
UNIT #1101 REPAIR LEAK AT SOUTH LAV DRAINAGE

1. WILL REQUIRE AUTHORIZATION TO DISCHARGE FROM PCDEQ ON SEWER, AND BACTERIA REPORT FOR POTABLE WATER SUPPLY
07/16/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO FINAL APPROVALS CAN BE GIVEN UNTIL ALL REQUIRED PLAN REVISIONS HAVE BEEN APPROVED BY THE CITY AND PROVIDED TO INSPECTOR FOR COMPARISON TO REDLINES PROVIDED BY CONTRACTOR. NEED ACCURATE REVISION FOR RWLS AT CORR. 246. STILL NEED REVS FOR:
1. WATER MAINS SEC B AND
2. WATER SCHEMATICS P6.1
3. CHANGES TO GAS SYSTEM REGULATOR LOCATIONS AND VENTING
4. FS AT SOFTENER
5. ACCESSIBLE SHOWER PIPING

HAMMER ARRESTORS REQUIRED AT WBS
SECURE DW's AND DW HOSES INSTALL CLIPS ON SINKS