Permit: T06CM06423

Parcel: 13320129C


Addresses:

6300 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Date Description Inspector Results Comments
05/15/2008 PLUMBING - SEWER HCS CONNECT Approved IVRS - Inspection :*
05/08/2008 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*
RECEIVED AUTHORIZATION TO DISCHARGE FOR SEWER PERMIT
05/07/2008 PLUMBING - SEWER HCS CONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
6" SEWER PIPING FROM BUILDING D TO MH #27 HAS BACKPITCH IN TWO LOCATIONS. PROVIDE 1/4" PER FOOT SLOPE UNLESS OTHERWISE SPECIFIED ON APPROVED PLANS.
COMPLETE SEWER PERMIT 1332
10/09/2007 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*
BUILDING D INSTALL OF 2-WAY CLEANOUT TO SITE SEWER STUB OK THIS HCS CONNECTION SHALL NOT BE TIED IN UNTIL AUTHORIZATION TO DISCHARGE FROM PCDEQ OR PIMA COUNTY IS APPROVED.