Permit: T06CM06423

Parcel: 13320129C


Addresses:

6300 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESS TEST FNL

Date Description Inspector Results Comments
10/24/2008 PLUMBING - GAS PRESS TEST FNL Approved IVRS - Inspection :*
10/09/2008 PLUMBING - GAS PRESS TEST FNL Not ready for Inspection IVRS - Inspection :*
10/01/2008 PLUMBING - GAS PRESS TEST FNL Not ready for Inspection IVRS - Inspection :*
COPPER NOT ALLOWED AT GAS LAMPS
GAS REGULATORS REQUIRE 5' CLEARANCE FROM SPARKS
09/30/2008 PLUMBING - GAS PRESS TEST FNL Partial Approval IVRS - Inspection :*
AFTER HRS. INSP. REQ. BY JAMES FROM SISSON PLUMBING
PAID W/CHK #'s -- 110624 & 110625 OPUS WEST CONST.

- GAS CLEARANCE PROVIDED
- OK TO USE KITCHEN EQUIPT.
- RECALL INSP. FOR PREVIOUSLY NOTED CORRECTIONS AND PLAN REVISIONS
09/29/2008 PLUMBING - GAS PRESS TEST FNL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SECURE GAS PIPING AT EQUIPT.
CORRECT SAFETY CABLES AT ROLLING APPLIANCES.
PROVIDE PROPER GAS REGULATOR TERMINATIONS.
PROVIDE PROTECTION FROM DAMAGE AT BBQ's
INSTALL SOVS
REMOVE HANDLES TO AREAS
NOT READY FOR GAS SERVICE
NEED TO INSP. BOILERS
09/26/2008 PLUMBING - GAS PRESS TEST FNL Partial Approval IVRS - Inspection :*