Permit: T06CM06423

Parcel: 13320129C


Addresses:

6300 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
10/09/2008 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
10/01/2008 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
WAITING ON PLAN REVISIONS
09/29/2008 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
PLAN REVS.
ALSO, HAVE MECHANICAL INSP. OF LAUNDRY AREA
09/26/2008 PLUMBING - GAS PRESSURE TEST Partial Approval GAS PRESSURE TESTING COMPLETE.
WILL SOAP TEST REGULATORS.
09/22/2008 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
GAS PIPING TO LAUNDRY NOT PER PLAN AS NOTED ON 3/13/08 CORRECT PIPING, REDLINE PLANS FOR INSPECTION
PROVIDE REV. MAKE CONN TO BUILDING C AND TEST FOR FINAL PRESSURE TEST.
09/19/2008 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
GAS TEST AT POOL FIRE PLACE OK
09/17/2008 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
09/15/2008 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
WRAPS ON GAS PIPING AT SERVICE
OK TO COVER
09/12/2008 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
YARD PIPING, OK TO COVER PE, WRAP IRON PIPE
09/11/2008 PLUMBING - GAS PRESSURE TEST Cancelled
08/15/2008 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
BARBEQUE PIPING AT KIT. OK PER REDLINES ON P5.1
PROVIDE ACCESS TO SOV
AT FINAL AND PLAN REVISION
GAS TO BARBEQUE AT TRELLIS OK
GAS TO POOL LIGHTS NOT SHOWN ON P6.5
06/27/2008 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
GAS TO GAS LIGHTS IN CACHE OK
06/26/2008 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
06/23/2008 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
GAS PIPING & REGULATOR LOCATIONS NOT PER PLAN
TEST MED. PSI PIPING TO 60 PSI AND LOW PRESSURE PIPING TO 10 PSI
04/11/2008 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
03/13/2008 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*