Permit: T06CM06423

Parcel: 13320129C


Addresses:

6300 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Date Description Inspector Results Comments
09/29/2008 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
11/28/2007 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
- CONNECTION OF DOMESTIC WATER AT BUILDING OK
- NEED TO SEE REVISED SITE PLAN

NOTE: WILL NEET WATER PIPING REVISIONS FOR INTERMEDIATE INSPECTIONS
10/10/2007 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
REDLINES OK - APPROVED REVISION NEEDED
10/09/2007 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
6" T/L COPPER FROM BUILDING EXTERIOR AT BUILDING B
STAIRWELL #2 NORTH OF ELEVATOR SHAFT TO STUB UP IN UNIT 1115 PER REDLINE ON SITE, REVISED CITY APPROVED WATER DISTRIBUTION PLAN SHALL BE REQUIRED.
10/03/2007 PLUMBING - YARD WTR LINE/TEST Cancelled
10/02/2007 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
CALL FOR INSP. WHEN READY
PLUMBER IS NOT USING THE PROPER TOOL FOR 6" BRAZED JOINTS. OXY/FUEL TORCHES ARE NEEDED TO CORRECTLY INSTALL 6" COPPER BRAZED JOINTS.
10/01/2007 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*
09/04/2007 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
6" CLASS 200 PVC INSTALLED FROM RP TO
TIE IN POINT 20' WEST