Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/13/2008 | PLUMBING - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 06/13/2008 | PLUMBING - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEC A; RWLS UNDER TEST BUT NOT INSTALLED PER PLAN AND INSTALLED WITH 270 DEG. CHANGE OF DIRECTIONS 2. REDLINE CHANGES AND PROVIDE PLAN REVISION 3. SECURE PIPING CLOSE TO DRAIN AND ON DROPS 4. OVERHEAD WATER AND GAS REQUIRES INSPECTION 5. DO NOT COVER |
|
| 04/08/2008 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* SEC B ABV CEILING PIPE INSULATION OK SEC B RAIN WATER PIPING OK |
|
| 03/03/2008 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 02/28/2008 | PLUMBING - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/26/2008 | PLUMBING - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/25/2008 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* AIR TEST ON PEX RMS 1101-1103 AND 1117 AND 1122-24 OK MAINTAIN TEST FOR 24 HRS. OK TO INSULATE TUBING PER SPEC. SECURE SHOWER DIVERTER VALVES |
|
| 02/13/2008 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK FOR FIRE ROCK AS LONG AS NO PLUMBING FITTINGS ARE COVERED PRIOR TO TEST & INSPECTION |
|
| 02/12/2008 | PLUMBING - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |