Permit: T06CM06423

Parcel: 13320129C


Addresses:

6300 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
10/13/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
CLOSET FLANGES COMPLETE
10/10/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
CLOSET FLANGES ALL EXCEPT 1163, 1151
10/09/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CLOSET FLANGES SEE D 1ST LEVEL SOUTH CORRIDOR OK
2) REQUESTED PLAN REVISIONS RECEIVED
3) PLANS REVISION OK
4) NEED TO CHECK GAS REGULATOR VENTS
10/07/2008 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
3" FITTINGS GLUED INSIDE 4" PIPE NOT ACCEPTABLE
ALSO, SECURE FLANGES
KEEP ALL OPEN PIPES CAPPED UNTIL FIXTURES ARE SET
09/29/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
09/22/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
SEC. D 2ND LEVEL CLOSET FLANGES AND
HAMMER ARRESTORS OK
09/17/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
CLOSET FLANGES A BUILDING 2ND LEVEL OK
RECEIVED PLAN REVS FOR ACCESSIBLE SHOWERS AND WATER PIPING. RWL REVISIONS ARE NOT ACCURATE.
09/12/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
C-SECTION CLOSET FLANGES OK
HAMMER ARRESTORS OK
A SECTION 3" OFFSET FLANGES GLUED INSIDE 4" PIPE;
PROVIDE FLANGE LISTING AND INSTALLATION INSTRUCTIONS.
09/03/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
- LAUNDRY WATER PIPING OK TO COVER
- 2215 & 2213 PIPING OK TO COVER
- REDLINE DELETED DRAIN AND REMOVE PIPING TO RE-VENT ON 3RD FLOOR
- PROVIDE PLAN REVISIONS PREVIOUSLY REQUESTED
09/02/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELED
08/29/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
08/28/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
BAR AREA OK
EMPLOYEE TR PIPE INSULATION OK TO COVER
08/26/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
EMPLOYEE RM. 108 DWV TEST OK
INSULATE WATER TUBING FOR REINSPECTION
BAR AREA: SEPARATE, INSULATE SECURE TUBING
IN LAUNDRY PROVIDE APPROVED CPVC TRANSITION FITTINGS FOR CONCEALED LOCATIONS
08/25/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
08/19/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
CW EXP LOOPS AT RMS. 1308 AND 1301 PER PSK19
DATED 7/28/08
08/08/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
2' LOOP ON CW, SEC D RM 1254
08/04/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
SEC. C 2ND LEVEL 2' OFFSET ON CW AT RM. 1233 OK
SEC. B 1ST LEVEL CLOSET FLANGES OK
SEC. B 2ND LEVEL HAMMER ARRESTORS OK
07/23/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
2ND LEVEL SEC. C CLOSET FLANGES OK
TEMP CAPS SHOULD BE INSTALLED UNTIL CLOSET IS SET TO PREVENT THE ESCAPE OF SEWER GASES INTO THE BUILDING
07/17/2008 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. THE PLAN REVISION REQUIRED AND REQUESTED ON FEB 20TH, MARCH 19TH, APRIL 17TH, MAY 15 AND 29TH WHICH WAS PROVIDED ON JULY 16TH FOR THE CHANGE OF MATERIAL TYPE ON THE MAIN DOMESTIC WATER DISTRIBUTION SYSTEM DOES NOT APPEAR TO SATISFY THE REQUIREMENTS OF THE 2003 UPC IS #20 SEC. 313.7; THERMAL EXPANSION
CPVC PIPING INSTALLED IN UNCONDITIONED ATTIC SPACE
BASED ON MY CONVERSATIONS WITH THE CITIES MECHANICAL ENGINEER AND DEPUTY DIRECTOR YOU ARE REQUESTED TO HAVE YOUR ENGINEER CONTACT ROBERT SHERRY @ 837-4914 TO RESOLVE THIS CONCERN OR NO APPROVALS WILL BE ISSUED.
07/11/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
SEC B LEVEL 3 CLOSET FLANGES OK
07/08/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
FLOOR DRAINS FOR RMS 2213, 2215, 2313, 2315 AND 2316 OK
FS PIPING FOR SOFTENER DRAIN RM 2315 OK
PROVIDE PLAN REV. FOR ADDITIONAL DRAINAGE
INSTALL TRAP PRIMER
WATER PIPING OK TO INSULATE
07/07/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
NOT READY PER JAMES SUPER NOT IN OFFICE
NOTE: DO NOT COVER GAS AND RWLS SEC. A UNTIL REDLINES HAVE BEEN PROVIDED AND COMPARED TO INSTALLATION.
07/02/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
CLOSET FLANGES 3RD LEVEL B BLD FROM SOUTH TO NORTH TO UNIT #1319 GOING WEST
06/27/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
CLOSET FLANGES 2ND LEVEL B OK
06/26/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
CLOSET FLANGES 2ND LEVEL B OK
WATER TEST TOILETS PRIOR TO CAULKING CONN TO FLOOR
06/24/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
4" FD PIPING FROM BOILER 1 ON ROOF. TEST OK.
RED LINE LOCATION OF DRAIN AND PIPING ON
APPROVED PLANS
06/23/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
SEC. D PIPE INSULATION OK. TEST ON TUBS & SHWRS OK
SEC. A PIPE INSULATION OK. TEST ON TUBS & SHWRS OK
06/19/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
SEC D - SOUTH & WEST SIDE PIPE INSULATION OK
SEC B - WEST END 2ND LEVEL, CLOSET FLANGES OK
06/18/2008 PLUMBING - INTERMEDIATE Partial Approval SEC D DWV TESTING OK
NEED TO SEE TEST OF TUBS & SHWRS
SEC A WATER MAINS OK TO INSULATE
06/16/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
SEC. A DWV W/TEST THRU ROOF OK
1ST LEVEL ABV CEILING OK
PROVIDE REDLINES AND REVISIONS FOR CHANGES TO RWLS
INCLUDE 270 DEG. CHANGES OF DIRECTION
CLOSET BOOTS SHALL BE BRASS OR EQUALLY CORROSION RESISTANT (STAINLESS)
06/13/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
SEC D 2ND LEVEL PIPE INSULATION AND STRAPPING OK
06/11/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
SEC D SOUTH OF 1154 INSULATION AND STRAPPING
OK TO COVER
RWL's RM. 1246 W/TEST OK
06/10/2008 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
ISOLATE PEX FROM METAL AND SECURE W/PIPE CLAMPS
SEAL JOINTS IN PIPE INSULATION W/ARMAFLEX 520 ADHESIVE
PROVIDE TEST OK RWL's AND SECURE VERTICAL DROPS
06/04/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
PIPE INSULATION IN CORRIDORS 227 AND 228 AND RMS ON BOTH SIDES OF CORRIDORS OK
06/03/2008 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
COMPLETE INSULATION
STRAP/SECURE TUBING
PAY ATTENTION TO LAUNDRY AND VENT SOVS
SECURE CPVC W/PROPER ALIGNMENT
USE CONTACT CEMENT TO SEAL JOINTS IN ARMORFLEX
05/30/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. KIT. RM 147 OK TO COVER WALLS
2. ABOVE CEILING GAS PIPING IS NOT RATED PER PLAN
3. PRESSURE REGULATOR IS NOT LOCATED PER PLAN
4. REDLINE ROUTING CHANGE ON APPROVED PLAN AND PROVIDE ENGINEER APPROVAL FOR CHANGE
5. ALSO, NEED TO INSPECT ABOVE CEILING PIPING SUPPORTS ON WATER, GAS AND DWV
6. FD AND PIPING IN CEILING ABV RM 1130 IS OK
7. PROVIDE 24" AP
8. BUILDING D EAST OF CONSTRUCTION CORRIDOR --
OK TO COVER
9. DO NOT COVER ANY PIPING WEST OF CORRIDOR
05/29/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
SEC. D WATER PIPING UNDER TEST.
PROVIDE APPROVED PLANS,
REDLINE LOOP OFFSET LOCATIONS, INSULATE, STRAP
AND SECURE ALL TUBING.
DWV CORRECTIONS OK.
SECURE PIPING. RECALL FOR INSP.

SEC. A RMS. 168, 268 DWV TEST THRU ROOF OK
RMS 168, 162-163 OK TO COVER
RMS 155-160 OK TO COVER
KITCHEN AREA CORRECT CW SIZING AT DISP. INSTALL
TRAP PRIMER DIST. OR SEPARATE TPS AND UNIONS.
PROVIDE ACCESS.
INSTALL GAS PIPING PER YOUR PIPING SCHEMATIC DRAWING
INSTALL MISSING PIPE SUPPORTS ON GAS, VENT AND WATER
05/28/2008 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SEC. A CORRECT WATER PIPE SIZING AND SUPPORTS
2. OK TO INSULATE
3. SUPPORT & SECURE PEX W/APPROVED PEX SUPPORTS
4. NO ADHESIVE TAPE
5. CO REQUIRED FOR MS
6. WYE PATTERN FITTINGS REQUIRED FOR FOOT VENTS ON ISLAND LOOPS
7. ABV CEILING AT BOILER LOCATION NEED AN ACCESS PANEL FOR CPVC THREADED CONNECTIONS; INSULATION AND SUPPORT
8. 4" FD IS NOT PROPERLY VENTED
05/27/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV W/TEST ON SEC. D
SOUTH OF 1154 OK EXCEPT FOR SLOPE IN RM 1150 AND SOME PIPE SUPPORTS NEEDED. STILL NEED WATER TEST ON SHOWERS AND TUBS.
05/23/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
05/15/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
- CORRECTIONS IN SEC. C OK
- SOME HANGERS INSTALLED ABV CEILING
- HAVE BEEN REMOVED FOR SHEETROCK
- RECALL FOR INSP. AFTER REINSTALLING HANGERS ON
TRAP ARMS
- PLEASE PROVIDE PLAN REVISIONS REQUESTED ON 3/19/08 FOR WATER DISTRIBUTION SYSTEM
05/08/2008 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
SEC. A NOT UNDER TEST. MISSING FHA STRAPS AND SUPPORTS
04/24/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV SEC C NORTH EXCEPT UNIT 1125 LEAK AT FLOOR OF LAUNDRY AND UNIT 1290 VENT BEHIND SHOWER
(1ST & 2ND LEVEL) WATER DISTRIBUTION & INSULATION OK
04/22/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELED
04/21/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
PM INSP REQUESTED
2PM CONTRACTOR NOT READY
04/18/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV SEC C SOUTH OF UNIT 1186 BOTH FLOORS TEST OK
INSULATE & SECURE HW PIPING
SUPPORT PIPING AS NEEDED
04/17/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
NOTE: ANY CHANGES MADE IN A SECTION SHALL BE INSPECTED. CPVC MAIN WATER DISTRIBUTION SEC. C INSTALLED PER ENGINEERS DIRECTIVE W/2' LOOP INSTALLED AT 100' ON HW ONLY
NEED PLAN REV. FOR FINAL APPROVAL
OK TO INSULATE ALL HW PIPING, STILL NEED TO SEE PIPING STRAPS. DWV TEST ON SOUTH HALF OF SEC. C
2ND LEVEL ONLY OK
1ST LEVEL REQUIRES CORRECTIONS & RETEST
SUPPORT PIPING
PLUMB. CLOSET RISERS
TEST TO SHOWER HEADS
FOAM WRAP AT SLAB
04/16/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/11/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
- BUILDING C PIPING W/TEST
- PROVIDE LETTER FOR CHANGE FROM WELDED TO THREADED FITTINGS ON 2" BLK PIPING
03/27/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
STILL NEED TO SEE HW MAIN PIPING INSULATION
SEAL JOINTS W/ADHESIVE
03/26/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
- 2ND & 3RD LEVEL PIPE INSULATIONS OK
- TUB & SHWRS OK
- RD'S TEST OK
- PIPING INSTALLED PER P.3.1.2
- RECALL FOR CORRECTION IN RM 1301 AND FOR PIPE SUPPORTS
03/24/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1ST LEVEL B SEC PIPE INSULATION OK
2ND LEVEL TEST ON TUBS & SHWRS OK
PROVIDE ACCESS AT CIRC. SETTERS
DO NOT STAPLE INSULATION TO DRAIN PIPING
03/19/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
CPVC WATER MAINS BUILDING B INSTALLED PER UNAPPROVED PSK-1B REV. PROVIDE CITY APPROVED PLAN REVISIONS WHICH INCLUDE MATERIAL TYPE AND METHODS USED TO CONTROL EXPANSION AND CONTRACTION OF CPVC. PEX INSTALLED PER DRAWING SUPPLIED BY TONY. ATTACH TO APPROVED SET AND PROVIDE PLAN REVISIONS FOR FINAL APPROVAL
03/18/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
03/17/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
BUILDING B DWV W/TEST THRU ROOF OK
EXCEPT FOR UNIT 1113
03/14/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
03/13/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV TEST TO LEVEL 3
GAS NOT PER PLAN

NOTE: ALL CHANGES FROM PLAN REQUIRE CITY APPROVED REVISIONS, REDLINES SHALL BE ON SITE FOR INSPECTIONS.
03/03/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV WATER TEST BUILD B ALL EXCEPT UNIT #1113
1ST LEVEL ONLY
02/28/2008 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
SOIL PIPING - TEST DOWN
WATER NOT PER PLAN
I NEED AT LEAST REDLINES TO INSPECT FROM
SEAL PIPE INSULATION
02/26/2008 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
DWV PIPING SHALL BE TESTED TO 10' ABOVE FITTINGS
AIR TEST ON PEX RMS 1116-1121
PEX WATER PIPING IS NOT INSTALLED PER P6.1
PROVIDE APPROVED PLAN REVISIONS
02/20/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO USE CPVC WATER PIPING AS NOTED BY L.PANOPIO
PROVIDE A DETAIL TO CONTROL EXPANSION AND CONTRACTION OF PLASTIC PIPING. REFERENCE UPC IS #20 SECTION 2.4
02/19/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
RECEIVED PLUMBING DIAGRAM W/NOTE ALLOWING CPVC WATER PIPING.
DO NOT COVER FITTINGS PRIOR TO TEST
WILL ALLOW AIR TEST ON PEX TUBING ONLY