Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/23/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/22/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* NEED PAPERWORK |
|
| 10/21/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK ALL OTHER ITEMS 1. NEED PLAN REVISIONS FOR LIGHTING CHANGES 2. NEED LETTER FOR LAUNDRY ROOM CHANGES |
|
| 10/20/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. VDV CABLING -- THERMOSTATE -- SUPPORT 725.24, 800.24 2. STAIRWELL EM LIGHTS 3. FINISH LAUNDRY ROOM EQUIPMENT INSTALLATION 4. NEED PLAN REVISION FOR CEILINGS |
|
| 10/16/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 10/15/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* OK "D" UNITS ROOF 1. FINISH ROOF PANELS AS DISCUSSED |
|
| 10/14/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK "D" CORRIDORS & UNITS OK KITCHEN EQUIPMENT "A" |
|
| 10/13/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 10/10/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK "C" ROOF & CORRIDORS 1 & 2 |
|
| 10/09/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK 'B' ROOF AND UNITS |
|
| 10/08/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 10/08/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* RECEIVED CHECKS: 111333 - $75.00 111497 - $75.00 111498 - $75.00 111499 - $75.00 TOTAL - $300.00 1. MISSING EXIT LIGHT B-2 2. NEED ILLUMINATION AT PANEL 3. BROKEN M/C CABLE SHEATHING 3-3 FIRE ALARM PANEL 4. NEED AIR HANDLER LOCKOUTS ALL UNITS 5. TIGHTEN CONDUCTOR TERMINATIONS B: FINISH OFFICES, LAUNDRY, BREAKROOM, STORAGE & EQUIPMENT AREAS ROOF: B 1. NEED PERMANENT LABELING FOR A/C UNITS & DISCONNECTS 2. NEED PANEL DIRECTORIES PER 408.4 3. TIGHTEN LOOSE FITTINGS ROOF: A 1. LABEL DISCONNECTING MEANS - PERMANENT 2. MAINTAIN WORKING CLEARANCES 110.26 A: CORDS FOR CABINET LIGHT NOT ACCESSIBLE 400.7 & 8 D: 1. NEED RANGES 2. LIGHT & SWITCH 1160 3. FINISH 1145, 1146, 1176, 1160 OK 1147-1175 EXCEPT AS NOTED |
|
| 10/07/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* BOND POLE POUR BASE OK 2-D EXCEPT 1251 & 1264 1276 RANGE ANTI-TIP |
|
| 10/04/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 10/03/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK ELEVATORS 1, 2, 3 TO MAIN DISCONNECT OK UNITS 1250-1273 EXCEPT AS NOTED RECEIVED CHECKS: 111328 - $75.00 111329 - $75.00 111330 - $75.00 TOTAL - $225.00 1. "2D": FLUSH FIRE ALARM SYSTEM |
|
| 10/02/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK ID TO TILE FOUNTAIN: 1. NEED GROUNDING ELECTRODE SYSTEM 2. NEED MAIN BREAKER NORTH COURTYARD: 1. PROPERLY GROUND POLES |
|
| 09/26/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 09/26/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* RECEIVED CHECKS: 110620 - $75.00 110621 - $75.00 110622 - $75.00 110623 - $75.00 TOTAL - $300.00 OK TO ROCK HARD LID C1 - D-1 C-2 - D-2 OK B HALLS EXCEPT AS NOTED OK C-1 UNIT EXCEPT AS NOTED 1140 SD's 1180 SD's 1. ILLUMINATION AT PANELS IN USE 2. MISSING EM LIGHT B-3 |
|
| 09/24/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK TO TILE C - 1ST FLOOR EXCEPT AT JUNCTION BOXES OK UNITS "B" EXCEPT AS NOTED RECEIVED CHECKS 110370 - $75.00 110371 - $75.00 110372 - $75.00 $225.00 1. UNIT 1111 LOCKED 2. CHECK SMOKE DETECTOR 1213 3. CHECK HALLS "B" |
|
| 09/23/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 09/22/2008 | ELECTRIC - FINAL | Not ready for Inspection | CONCRETE ENCASEMENT 2" TOP, BOTTOM AND SIDES OK PVC ACROSS ROAD AND BOLLARDS EAST OK BOLLARDS BASES EAST OK POLES AND BOLLARDS BASES SOUTH |
|
| 09/20/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* OK 2 POLE BASES SOUTHWEST OK C-1, D-1, C-2, D-2 HALLS "A" KITCHEN 1. VERIFY LISTING ALL KITCHEN EQUIPMENT 2. ALL KITCHEN RECEPTACLES TO BE GFI 210.8 3. RECEPTACLES UNDER HOOD TO SHUT OFF WITH ANSUL 4. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM PANELS THEATER: 1. DISCONNECTING MEANS FOR SCREEN MOTOR "A": 1. OPEN SPLICES IN CORDS - CORD NOT ALLOWED FOR PERMANENT WIRING - 400.7 2. BOXES MORE THAN 1/4" - 314.20 ALSO LIGHTS 3. USE APPROVED HARDWARE FOR DEVICES - NOT DRYWALL SCREWS 4. GROUND FIXTURE HARDWARE 5. PANEL DIRECTORIES PER 408.4 - NO ABBREVIATIONS 6. SOME EM LIGHTS NOT WORKING "C": 1. BOXES MORE THAN 1/4" - 314.20 2. GFCI NOT WORKING 3. RECEPTACLE WIRING INCORRECT 4. MISSING PANEL DIRECTORIES OR INCORRECTLY LABELED 5. MISSING RECEPTACLE SERVING COUNTERTOP - 210.52 6. GROUND FIXTURE HARDWARE & BACK PLATES 7. MAKE UP BATH BAR IN BOX AS PER MANUFACTURE INSTRUCTIONS 8. LABEL GFCI RECEPTACLES 9. LOCKOUTS FOR AIR HANDLERS *CHECK HALL EM & EXITS NEXT TIME & ROOF WHERE ARE REVISED SERVICE PLANS AS DISCUSSED WITH TOM STEVENS IN JULY? "B": 1. CEILING BOXES MORE THAN 1/4" - 314.20 ALSO, OUTSIDE LIGHTS 2. GROUND FIXTURE HARDWARE 3. SEE WRITE UP FOR "C" RECEIVED CK#108628 FOR $75.00, #110373 FOR $150.00, 110374 FOR $150.00 -- TOTAL $375.00 |
|
| 09/19/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 09/09/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. OK CEILINGS KITCHEN, 260, 259, 251, 252, 250, 249, 248, 247, 246A, 260A 2. OK HARD LID 1ST FLOOR D BLDG. 3. OK U.G POLE LIGHTS WEST LOT 4. OK 3 POLE BASES ALONG WALK WEST SIDE MAIN ENTRY |
|
| 08/19/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK 1101 & 1124 SUBJECT TO OTHER INSPECTORS |
|
| 08/18/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. USE APPROVED HARDWARE WITH DEVICES - NOT DRYWALL SCREWS 110.3 2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20 3. GROUND BATH BAR BACK PLATES 4. FAN COIL BREAKERS NOT SIZED CORRECTLY 5. CLEAN DIRT & FOREIGN MATERIAL FROM PANEL (2ND TIME) 6. RANGE BREAKER AMPACITY FOR #8 NM CABLE - 334.80 |
|
| 08/16/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 07/21/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* FINISH ELECTRIC |
|
| 07/19/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 07/18/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 07/17/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 07/14/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK UNITS 1104-1107, 1120-1123, 1204-1207, 1220-1223, 1304-1307, 1320-1323 TEMP POWER FOR TEST 1. CLEAN EXCESS DIRT FROM PANEL 2. CAP HOOD WIRES 3. PANEL MORE THAN 1/4" BOX TO SURFACE *NOTE: 314.20 WILL APPLY *NOTE: 440.14 WILL APPLY RECEIVED MONEY ORDER #57968348382 --- $150.00 |
|
| 07/10/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BRACE CABLES FOR LINE CONDUCTORS AS PER MANUFACTURES INSTRUCTIONS 2. CONTRACTOR TO MAINTAIN LOCK OUT/TAG OUT 3. NEED LETTER OF TORQUE B:SES |
|
| 07/08/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK 2D CORRIDOR WALLS & LIDS 2. CHECKED DEVICES INSTALLED & PANEL MAKEUP IN ROOMS 1124, 1224, 1324, 1101-1103, 1201-1203, 1301-1303 ALL OK |
|
| 07/07/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 07/03/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1. BUILDING INSPECTOR TO VERIFY FIRE STOPPING BETWEEN FLOORS 2. SUPPORT VDV CABLING 725.24, 800.24 3. PROTECT VDV CABLING FROM SHARP METAL EDGES 4. VERIFY CONCRETE ENCASEMENT OF MC CABLES 5. SUPPORT M/C CABLE ON VERTICAL |
|
| 07/02/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* OK DINING ROOM CEILING 1. FILL UNUSED OPENINGS 2. PROTECT M/C CABLES 3. SECURE M/C STUDS UPON EXITING WALLS 4. PROVIDE BACK BRACING 314.23 5. M/C TO BE SUPPORTED CORRECTLY |