Permit: T06CM06423

Parcel: 13320129C


Addresses:

6300 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/23/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/22/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NEED PAPERWORK
10/21/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK ALL OTHER ITEMS

1. NEED PLAN REVISIONS FOR LIGHTING CHANGES
2. NEED LETTER FOR LAUNDRY ROOM CHANGES
10/20/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. VDV CABLING -- THERMOSTATE -- SUPPORT 725.24, 800.24
2. STAIRWELL EM LIGHTS
3. FINISH LAUNDRY ROOM EQUIPMENT INSTALLATION
4. NEED PLAN REVISION FOR CEILINGS
10/16/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/15/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
OK "D" UNITS ROOF

1. FINISH ROOF PANELS AS DISCUSSED
10/14/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK "D" CORRIDORS & UNITS
OK KITCHEN EQUIPMENT "A"
10/13/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
10/10/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK "C" ROOF & CORRIDORS 1 & 2
10/09/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK 'B' ROOF AND UNITS
10/08/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
10/08/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
RECEIVED CHECKS:
111333 - $75.00
111497 - $75.00
111498 - $75.00
111499 - $75.00
TOTAL - $300.00

1. MISSING EXIT LIGHT B-2
2. NEED ILLUMINATION AT PANEL
3. BROKEN M/C CABLE SHEATHING 3-3 FIRE ALARM PANEL
4. NEED AIR HANDLER LOCKOUTS ALL UNITS
5. TIGHTEN CONDUCTOR TERMINATIONS

B: FINISH OFFICES, LAUNDRY, BREAKROOM, STORAGE & EQUIPMENT AREAS

ROOF: B
1. NEED PERMANENT LABELING FOR A/C UNITS & DISCONNECTS
2. NEED PANEL DIRECTORIES PER 408.4
3. TIGHTEN LOOSE FITTINGS

ROOF: A
1. LABEL DISCONNECTING MEANS - PERMANENT
2. MAINTAIN WORKING CLEARANCES 110.26

A: CORDS FOR CABINET LIGHT NOT ACCESSIBLE 400.7 & 8

D:
1. NEED RANGES
2. LIGHT & SWITCH 1160
3. FINISH 1145, 1146, 1176, 1160

OK 1147-1175 EXCEPT AS NOTED
10/07/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
BOND POLE POUR BASE

OK 2-D EXCEPT 1251 & 1264


1276 RANGE ANTI-TIP
10/04/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/03/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK ELEVATORS 1, 2, 3 TO MAIN DISCONNECT
OK UNITS 1250-1273 EXCEPT AS NOTED

RECEIVED CHECKS:
111328 - $75.00
111329 - $75.00
111330 - $75.00
TOTAL - $225.00

1. "2D": FLUSH FIRE ALARM SYSTEM
10/02/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK ID TO TILE

FOUNTAIN:
1. NEED GROUNDING ELECTRODE SYSTEM
2. NEED MAIN BREAKER

NORTH COURTYARD:
1. PROPERLY GROUND POLES
09/26/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
09/26/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
RECEIVED CHECKS:
110620 - $75.00
110621 - $75.00
110622 - $75.00
110623 - $75.00
TOTAL - $300.00

OK TO ROCK HARD LID
C1 - D-1
C-2 - D-2
OK B HALLS EXCEPT AS NOTED
OK C-1 UNIT EXCEPT AS NOTED

1140 SD's
1180 SD's

1. ILLUMINATION AT PANELS IN USE
2. MISSING EM LIGHT B-3
09/24/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK TO TILE C - 1ST FLOOR EXCEPT AT JUNCTION BOXES
OK UNITS "B" EXCEPT AS NOTED

RECEIVED CHECKS 110370 - $75.00
110371 - $75.00
110372 - $75.00
$225.00

1. UNIT 1111 LOCKED
2. CHECK SMOKE DETECTOR 1213
3. CHECK HALLS "B"
09/23/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
09/22/2008 ELECTRIC - FINAL Not ready for Inspection CONCRETE ENCASEMENT 2" TOP, BOTTOM AND SIDES

OK PVC ACROSS ROAD AND BOLLARDS EAST
OK BOLLARDS BASES EAST
OK POLES AND BOLLARDS BASES SOUTH
09/20/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
OK 2 POLE BASES SOUTHWEST
OK C-1, D-1, C-2, D-2 HALLS

"A" KITCHEN
1. VERIFY LISTING ALL KITCHEN EQUIPMENT
2. ALL KITCHEN RECEPTACLES TO BE GFI 210.8
3. RECEPTACLES UNDER HOOD TO SHUT OFF WITH ANSUL
4. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM PANELS

THEATER:
1. DISCONNECTING MEANS FOR SCREEN MOTOR

"A":
1. OPEN SPLICES IN CORDS - CORD NOT ALLOWED FOR PERMANENT WIRING - 400.7
2. BOXES MORE THAN 1/4" - 314.20 ALSO LIGHTS
3. USE APPROVED HARDWARE FOR DEVICES -
NOT DRYWALL SCREWS
4. GROUND FIXTURE HARDWARE
5. PANEL DIRECTORIES PER 408.4 - NO ABBREVIATIONS
6. SOME EM LIGHTS NOT WORKING

"C":
1. BOXES MORE THAN 1/4" - 314.20
2. GFCI NOT WORKING
3. RECEPTACLE WIRING INCORRECT
4. MISSING PANEL DIRECTORIES OR INCORRECTLY LABELED
5. MISSING RECEPTACLE SERVING COUNTERTOP - 210.52
6. GROUND FIXTURE HARDWARE & BACK PLATES
7. MAKE UP BATH BAR IN BOX AS PER MANUFACTURE INSTRUCTIONS
8. LABEL GFCI RECEPTACLES
9. LOCKOUTS FOR AIR HANDLERS

*CHECK HALL EM & EXITS NEXT TIME & ROOF
WHERE ARE REVISED SERVICE PLANS AS DISCUSSED WITH
TOM STEVENS IN JULY?

"B":
1. CEILING BOXES MORE THAN 1/4" - 314.20
ALSO, OUTSIDE LIGHTS
2. GROUND FIXTURE HARDWARE
3. SEE WRITE UP FOR "C"

RECEIVED CK#108628 FOR $75.00, #110373 FOR $150.00,
110374 FOR $150.00 -- TOTAL $375.00
09/19/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
09/09/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. OK CEILINGS KITCHEN, 260, 259, 251, 252, 250, 249,
248, 247, 246A, 260A
2. OK HARD LID 1ST FLOOR D BLDG.
3. OK U.G POLE LIGHTS WEST LOT
4. OK 3 POLE BASES ALONG WALK WEST SIDE MAIN ENTRY
08/19/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK 1101 & 1124 SUBJECT TO OTHER INSPECTORS
08/18/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. USE APPROVED HARDWARE WITH DEVICES - NOT DRYWALL SCREWS 110.3
2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20
3. GROUND BATH BAR BACK PLATES
4. FAN COIL BREAKERS NOT SIZED CORRECTLY
5. CLEAN DIRT & FOREIGN MATERIAL FROM PANEL (2ND TIME)
6. RANGE BREAKER AMPACITY FOR #8 NM CABLE - 334.80
08/16/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
07/21/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
FINISH ELECTRIC
07/19/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
07/18/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
07/17/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
07/14/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK UNITS 1104-1107, 1120-1123, 1204-1207, 1220-1223,
1304-1307, 1320-1323

TEMP POWER FOR TEST

1. CLEAN EXCESS DIRT FROM PANEL
2. CAP HOOD WIRES
3. PANEL MORE THAN 1/4" BOX TO SURFACE

*NOTE: 314.20 WILL APPLY
*NOTE: 440.14 WILL APPLY

RECEIVED MONEY ORDER #57968348382 --- $150.00
07/10/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. BRACE CABLES FOR LINE CONDUCTORS AS PER MANUFACTURES INSTRUCTIONS
2. CONTRACTOR TO MAINTAIN LOCK OUT/TAG OUT
3. NEED LETTER OF TORQUE

B:SES
07/08/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK 2D CORRIDOR WALLS & LIDS
2. CHECKED DEVICES INSTALLED & PANEL MAKEUP IN
ROOMS 1124, 1224, 1324, 1101-1103, 1201-1203, 1301-1303
ALL OK
07/07/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
07/03/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1. BUILDING INSPECTOR TO VERIFY FIRE STOPPING BETWEEN FLOORS
2. SUPPORT VDV CABLING 725.24, 800.24
3. PROTECT VDV CABLING FROM SHARP METAL EDGES
4. VERIFY CONCRETE ENCASEMENT OF MC CABLES
5. SUPPORT M/C CABLE ON VERTICAL
07/02/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
OK DINING ROOM CEILING

1. FILL UNUSED OPENINGS
2. PROTECT M/C CABLES
3. SECURE M/C STUDS UPON EXITING WALLS
4. PROVIDE BACK BRACING 314.23
5. M/C TO BE SUPPORTED CORRECTLY