Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/20/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 10/17/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* *CHECK STAIRWELLS OK OUTER PERIMETER LIGHTING EXCEPT AS NOTED 1. GROUND AND BOND POLES AS DISCUSSED |
|
| 10/02/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 10/01/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 09/29/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 09/26/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 09/24/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* RECEIVED CK#10233 - $150.00 C: 1. CORRECT PANEL DIRECTORIES 2. AIR HANDLER DISCONNECTING MEANS OK 2ND FLOOR "C" UNITS ONLY EXCEPT AS NOTED OK HARD LID 2 "C" ELEVATOR |
|
| 09/15/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 09/10/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 09/09/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 09/08/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 09/04/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 09/03/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 08/29/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 08/28/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* OK "D" BUILDING ROOMS 1114-1117 OK 3/4" PVC IN FRONT OF DUMPSTER ONLY 1. FINISH KITCHEN |
|
| 08/25/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio |
|
| 08/21/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 08/20/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 08/18/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 08/14/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 08/13/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 07/24/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK 1 & 3 FLOORS "B" HALLS |
|
| 07/23/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
| 07/21/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 07/19/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 07/14/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* OK 3/4 PVC BLDG TO STAIRWELL UNDER SLAB 1. SUPPORT VDV CABLING 725.24, 800.24 2. SUPPORT M/C AS PER CODE 6' INTERVALS 3. PROTECT VDV CABLING AT STUDS |
|
| 07/11/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. FINISH GRID 2. SECURE FIXTURE SECURELY TO GRID - 410.16 3. CORDS NOT ALLOWED ABOVE CEILING - 400.7 & 8 4. SUPPORT WIRES NEEDED FOR EXIT LIGHTS *NOTE: A REFEE WILL BE ASSESSED FOR UNNECESSARY INSPECTIONS IN THE FUTURE 5. M/C NOT TO BE TIED TO GRID 6. BOND 8X8 GUTTER ENCLOSURES 7. CLOSE 4SQ. BOXES 8. MOVE TEMP LIGHTS OUT OF GRID |
|
| 07/02/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 06/27/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 03/18/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK 1ST LID 1225-1244 & 1278-1291 |
|
| 02/27/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK 1ST ROCK 2ND FLOOR 1245-1276 |
|
| 02/21/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* BUILDING D 2ND FLOOR 1. RUN BRANCH CIRCUIT FOR ROOFTOP CONDENSING UNITS FROM 1ST FLOOR 2. INSTALL PROTECTIVE BUSHING ON EMT WHERE ROMEX ENTERS FOR CONDENSING UNITS - NEC 300.15 |
|
| 02/20/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* BLDG D FIRST CEILINGS OK |
|
| 02/19/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK PRE-ROCK & INSULATION BUILDING "B" THIRD FLOOR CEILING |
|
| 02/13/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 02/12/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* REMOVE INSULATION TO VIEW WIRING FOR INSPECTION |
|
| 01/29/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. PVC CONDUIT TO BE AS PER 352.12(D) OK 1ST LIDS 1301-1324 *SUPPORT NM WITHIN 12" |
|
| 01/25/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* NEED ACCESS TO THIRD FLOOR |
|
| 01/24/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK 1ST LID 1201 - 1224 1. STAPLE STUBS |
|
| 01/22/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK 4" STUB ELEVATOR ROOM OK 1ST LID 1101-1124 |