Permit: T06CM06423

Parcel: 13320129C


Addresses:

6300 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
10/20/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
10/17/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
*CHECK STAIRWELLS

OK OUTER PERIMETER LIGHTING EXCEPT AS NOTED

1. GROUND AND BOND POLES AS DISCUSSED
10/02/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
10/01/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
09/29/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
09/26/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
09/24/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
RECEIVED CK#10233 - $150.00

C:
1. CORRECT PANEL DIRECTORIES
2. AIR HANDLER DISCONNECTING MEANS

OK 2ND FLOOR "C" UNITS ONLY EXCEPT AS NOTED

OK HARD LID 2 "C" ELEVATOR
09/15/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
09/10/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
09/09/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
09/08/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
09/04/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
09/03/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
08/29/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
08/28/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
OK "D" BUILDING ROOMS 1114-1117
OK 3/4" PVC IN FRONT OF DUMPSTER ONLY

1. FINISH KITCHEN
08/25/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
08/21/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
08/20/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
08/18/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
08/14/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
08/13/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
07/24/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK 1 & 3 FLOORS "B" HALLS
07/23/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
CANCELED
07/21/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
07/19/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
07/14/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
OK 3/4 PVC BLDG TO STAIRWELL UNDER SLAB

1. SUPPORT VDV CABLING 725.24, 800.24
2. SUPPORT M/C AS PER CODE 6' INTERVALS
3. PROTECT VDV CABLING AT STUDS
07/11/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. FINISH GRID
2. SECURE FIXTURE SECURELY TO GRID - 410.16
3. CORDS NOT ALLOWED ABOVE CEILING - 400.7 & 8
4. SUPPORT WIRES NEEDED FOR EXIT LIGHTS

*NOTE: A REFEE WILL BE ASSESSED FOR UNNECESSARY INSPECTIONS IN THE FUTURE

5. M/C NOT TO BE TIED TO GRID
6. BOND 8X8 GUTTER ENCLOSURES
7. CLOSE 4SQ. BOXES
8. MOVE TEMP LIGHTS OUT OF GRID
07/02/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
06/27/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
03/18/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK 1ST LID 1225-1244 & 1278-1291
02/27/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK 1ST ROCK 2ND FLOOR
1245-1276
02/21/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
BUILDING D 2ND FLOOR
1. RUN BRANCH CIRCUIT FOR ROOFTOP CONDENSING UNITS FROM 1ST FLOOR
2. INSTALL PROTECTIVE BUSHING ON EMT WHERE ROMEX ENTERS FOR CONDENSING UNITS - NEC 300.15
02/20/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
BLDG D FIRST CEILINGS OK
02/19/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK PRE-ROCK & INSULATION BUILDING "B" THIRD FLOOR CEILING
02/13/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
02/12/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
REMOVE INSULATION TO VIEW WIRING FOR INSPECTION
01/29/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. PVC CONDUIT TO BE AS PER 352.12(D)

OK 1ST LIDS 1301-1324

*SUPPORT NM WITHIN 12"
01/25/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
NEED ACCESS TO THIRD FLOOR
01/24/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK 1ST LID 1201 - 1224
1. STAPLE STUBS
01/22/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK 4" STUB ELEVATOR ROOM
OK 1ST LID 1101-1124