Permit: T06CM06423

Parcel: 13320129C


Addresses:

6300 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
10/20/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
10/01/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 2ND FLOOR "D" HALL
OK LIGHTS AT SOUTH CANOPY
OK BONDING FOR BOLLARD - 680.26
09/20/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
09/19/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
09/10/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK POLE BASES @ CIRCLE DRIVEWAY
2. OK CEILING CORRIDOR BLDG. C - 2ND FLOOR
3. OK WALLS & CEILINGS STAIRCASE #7
09/08/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK U.G FOR SPOT LIGHT NORTH SIDE
OF BUILDING (6) TOTAL
2. OK CEILING KITCHEN EXCEPT AREA BY DINING ROOM
3. OK WALLS & CEILINGS AT 3RD FLOOR ELEVATOR LOBBY AND WATER SOFTENER RM
08/29/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
08/28/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
08/25/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
PLEASE PAY REINSPECTION FEE BEFORE NEXT INSPECTION

1. FINISH VDV
2. FINISH ABOVE CEILING AS LAST INSPECTION
08/22/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS & LID SES "D"
08/21/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
08/20/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
KITCHEN
1. FINISH M/C CABLES
2. SUPPORT M/C AS PER 300.11
3. SUPPORT M/C TO OUTLET BOX 12"
4. FINISH SUPPORTING FIRE ALARM CABLE
5. A/C DISCONNECT TO BE ACCESSIBLE AND LABELED

1C/1D: OK DROPS HARD LIDS

LEAVE ACCESS TO CHECK BOND LUG TO FIRE PIPE
08/19/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
08/18/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
08/16/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) FINISH STAIR #2 PER INSPECTION ON 8/14/08
2) CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM PANELS
3) TIGHTEN MAIN LUG TERMINATIONS AND ALL ALUMINUM
4) FILL UNUSED OPENINGS IN PANELS
5) RECEIVED CHECKS #108626 FOR $150 & CHECK #108627 FOR $75
6) 314.20 ON LIGHT BOXES IN CEILING
7) OK STAIRWELL #1
8) OK PVC UNDER POOL ROOM
9) OK PVC EAST OF PALM TREES SOUTH COURTYARD
10) OK TMPP 1125-1141, 1180-1190, 1226-1244 AND 1277-1290 EXCEPT 1133-1183
08/15/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
08/14/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
STAIR #2: SUPPORT FIRE ALARM CABLE 760.24

#1C:
1. SUPPORT VDV CABLING 725.24
2. REMOVE TEMP LIGHT
3. USE APPROVED LISTED ADAPTOR FOR BOND CLAMP

#1A
1. SUPPORT FIXTURE WHIP OFF OF GRID
2. ATTACH FIXTURE 410.16
08/13/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK PVC AT PALM TREES SOUTH COURTYARD

1. NEED LISTING OF TORQUE SES "C"
08/11/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
UNDERGROUND COVERED IN COURTYARD WITHOUT INSPECTIONS - PUT HOLE AS DISCUSSED
08/08/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
08/07/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK 137 & 134 ROUGH
2) OK 2C HARD LIDS
08/05/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
08/04/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK UNITS 1160-1166
08/01/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. MAINTAIN FIRE WALL SEPARATION
2. SUPPORT NM CABLES ABOVE PANEL
07/31/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
A REFEE WILL BE ASSESSED FOR UNNECESSARY INSPECTIONS PER ADMIN. CODES
07/30/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
NO WORK PROGRESS
07/29/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK UNITS 1157-1159 & 1167
07/28/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. MAINTAIN FIRE WALL SEPARATIONS AT BATH LIGHTS

OK UNITS 1151-1156; 1168-1171 --- AFTER CORRECTIONS
07/25/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELED
07/24/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1145-1150
1176-1172

OK ROUGH UNITS 1145-1150/1172-1176

RECEIVED CHECK #0606743797 - $1,500.00
07/18/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
07/17/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
OK TEMP POWER 1108-1110, 1117-1119, 1208-1210, 1217-1219
1308-1310, 1317-1319

1. CLEAN EXCESS DIRT FROM PANELS
07/15/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 2-A HARD LID
07/08/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
07/07/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS 2A COMMON AREA
07/03/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
DENIED 2A
PARTIAL 2D
OK 1210-1266
07/02/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
07/01/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 1259 & 1267
06/30/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELED
06/27/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. SUPPORT VDV ABOVE CEILING 2D ELECTRIC ROOM
OK 2D CORRIDOR LID ONLY
06/26/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK "D" CORRIDOR CENTER TO AROUND AND END 1257
06/24/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK DINING ROOM WALLS ONLY

1250-1255 OK ROUGH
1269-1271 OK ROUGH
06/23/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
06/19/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 2C SOUTHEAST STAIRWELL & ELECTRIC ROOM
OK ENTRY ARCH RESTAURANT
06/18/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 1245-1249
1272-1276
06/16/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ENTRY
PORTE CACHE

1. POTHOLE UNDERGROUND CONDUITS FOR INSPECTION
06/11/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. FINISH BISTRO ENTRANCE

OK 1A HARD LID EXCEPT AS NOTED
06/05/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 3B SOFFITS

1. BRING FIRE ALARM INTO BOX
06/03/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
FINISH ELECTRIC AND VDV CABLING 3B
06/02/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROUGH 1139-1141, 1180-1182
05/30/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1132-1138
1183-1187

OK UNITS 1132-1138/1183-1187 ROUGH

1. GROUND JUNCTION BOXES FOR LIGHTS
05/29/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. FURR OUT 1191

OK 1125-1131 1188-1191 ROUGH EXCEPT 1191 PANEL
05/28/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK #2 CORRIDOR B-C
OK #1 CORRIDOR A,B,C

1. FINISH UNITS
05/27/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK NORTH EXTERIOR
1160-1163 AND 1260-1263 ONLY
NO MORE PARTIAL ROOMS FINISH UNITS TO INSPECT
05/23/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS 1A
OK CORRIDOR 2C
05/22/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK 2-1 1/2" GATE ACCESS RACEWAYS
2) DO NOT ROCK
3) VDV CABELING TO BE SUPPORTED TO STRUCTURE NOT OFF OF OTHER WIRING METHODS
4) FINISH ALL WIRING TO ROOMS (VDV)
05/21/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
VERIFY COAX CABLE HARD LINE FOR LISTING
05/20/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
EXTERIOR WALLS TO COURTYARD ONLY
#1125-1129
05/19/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROTECT VDV CABLING FROM SHARP METAL EDGES
2. SUPPORT VDV CABLING

OK WALLS ONLY
CORRIDOR 2C
05/15/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. PROPERLY SUPPORT CONDUITS
2. TIGHTEN LOOSE FITTINGS
05/14/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK UNITS 1238-1244
1277-1282
05/13/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 1207, 1230-1237, 1283-1286
05/12/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELED
05/09/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROUGH
1225-1229
1288-1291
05/08/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. SUPPORT FIRE ALARM CABLES WITHIN 8" OF BOXES
2. SUPPORT NM CABLE 12" PANEL AND ENTRY TO FLEX
3. FIRE WALL SEPARATIONS
4. BACK BRACES FOR 4-GANG BOXES
5. MISSING EXHAUST FANS
05/06/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. INSTALL FITTING INTO BOX
2. BOXES OVERFILLED AT CANS

OK 1ST FLOOR CORRIDOR "B"
AFTER CORRECTIONS
05/02/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
602-725-0607

OK 2ND FLOOR OFFICES & HALL HARD LIDS
OK 3RD FLOOR PRE-ROCK HALL LID
05/01/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
3RD FLOOR
1. MAINTAIN FIREWALL SEPARATION
2. SUPPORT FIRE ALARM CABLE AT BOXES

2ND FLOOR
1. DRYWALL NOT ALL REMOVED

PLEASE PAY REFEE AS DISCUSSED
04/30/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SUPPORT VDV CABLING
2. REMOVE OFFICE CEILINGS TO INSPECT 2ND FLOOR
3. FINISH HALL 2ND FLOOR
4. VERIFY FIRESTOPPING INSPECTION

*314.20 WILL APPLY
04/29/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK UNITS 1109-1117
04/28/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1106-1109
1117-1121
04/25/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/24/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK UNITS 1124, 1123, 1102, 1122, 1104, 1105 "B" FIRST FLOOR
04/23/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 3RD FLOOR INTERIOR BUILDING B
04/22/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS & HARD CEILINGS 1301-1307/1320-1324
04/21/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
MAINTAIN FIRE SEPARATION

OK 2ND FLOOR CORRIDOR BUILDING "B"
04/18/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
MAINTAIN FIRE WALL SEPARATION - 300.21
04/15/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 1101 & 1103 MODELS
04/14/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
MAINTAIN FIREWALL SEPARATION OF BOXES

OK 2ND FLOOR 1201-1206, 1220-1224 (11 UNITS)
04/11/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK FLEX & CONDUIT LIVING BUILDINGS
04/10/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK VDV CABLING EAST 1/2 2ND FLOOR ROOMS
04/09/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SUPPORT VDV CABLING AS PER 725.6, 800.6, 760.6
2. PROTECT VDV CABLING AT MEDIA CENTERS
04/07/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ELEVATOR #3 WALLS & HARD CEILING
04/04/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS ELEVATOR ROOM
OK 2 GROUND RODS & #4 SDBC
04/03/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
DO NOT DRY WALL

1. ELEVATOR ROOM - FINISH FLEX CONDUIT THROUGH STUDS
2. SUPPORT T-STAT WIRES IN WALL AND ABOVE CEILING 725.6

OK 120V M/C CABLE & BOXES
03/24/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELED
03/21/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. FINISH HALLWAY WIRING
2. SECURE CABLE TO METAL BOXES - TIGHTEN CLAMPS
3. VERIFY USAGE OF EMT THROUGH FIRE WALLS AND LISTING FOR FITTINGS
4. FINISH WIRING CLOSET LIGHT #1111
5. CLOSET LIGHT S/L DAMAGED #1108
6. SECURE CABLE TO BOXES - MULTIGANG
7. WIRING DAMAGED #1107, 1106
8. WIRE SHEATHING TO EXTEND 1/4" INTO BOXES #1106
03/20/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
03/17/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK EXTERIOR WALLS 1301-1324 ONLY
03/14/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK EXTERIOR WALLS 2ND FLOOR
03/13/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. HAVE BUILDING INSPECTOR VERIFY FIRESTOPPING
TOP PLATES & WALLS
2. PROTECT NM CABLE AT STUDS

OK 1101-1124 AFTER CORRECTIONS
EXTERIOR WALLS ONLY
12/06/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 7 - 4" CONTINUATION TO BUILDING "A"

1. STRAP NM CABLES ABOVE PANEL 12"

*NEED TO SEE ELECTRICAL WIRING BEFORE 1ST LID
(PRE-ROCK)