Permit: T06CM06423

Parcel: 13320129C


Addresses:

6300 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
10/20/2008 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
09/22/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
CONCRETE ENCASEMENT 2" TOP, BOTTOM AND SIDES

OK PVC ACROSS ROAD AND BOLLARDS EAST
OK BOLLARDS BASES EAST
OK POLES AND BOLLARDS BASES SOUTH
09/20/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
09/19/2008 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
09/18/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK POLE & BOLLARD
SOUTH COURTYARD BASES

OK POLE & BOLLARDS SOUTH EAST AND SOUTH WEST
09/15/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK POLE BASES SOUTH COURTYARD
2. OK POLE BASE CORNER OF DRIVEWAY @ SPEEDWAY
09/12/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK POLE BASES NORTH COURTYARD & EAST SIDE OF SOUTH COURTYARD
09/10/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
09/09/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
09/08/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
09/04/2008 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
09/03/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. SUPPLEMENTAL ELECTRODE CONDUCTOR TO BE AS STRAIGHT AS POSSIBLE
2. UNCOVER ACROSS ROAD AS DISCUSSED

OK "2D" HARD LIDS
OK 2ND FLOOR BAR
08/29/2008 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
OK TO TILE "A"
138-141, 164-166, 168, 154
08/28/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
08/21/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK SOUTH COURTYARD PVC
OK LAUNDRY ROOM WALLS
08/13/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
08/12/2008 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. ALL CONDUITS TO BE AS PER 300.5
2. UNCOVER POWER TO POOL EQUIPMENT TO INSPECT
08/08/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK FRONT POLE TO POLE AND BUILDING UNDER PAVEMENT

OK "D" STAIR #3
08/05/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK PVC FOR FRONT FOUNTAIN
OK #4 TO REBAR
OK ID CORRIDOR
07/28/2008 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
07/14/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
03/27/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. UNCOVER PVC CONDUIT AT FRONT DRIVE THRU OUTSIDE BUILDING

OK 2ND FLOOR - FLOOR BOX LOBBY
03/12/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 5 FLOOR BOXES & CONDUIT "A" BUILDING
1ST FLOOR SLAB
03/06/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK FEEDER & BRANCH CIRCUITS
PVC UNDER SLAB "A" LOBBY & KITCHEN

1. FINISH FLOOR BOXES & CONDUIT
02/13/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 15 - 4" PVC TO SES "A" & SES "B"

* NEED MARKING TAPE PER 300.5

NEED INSULATION REMOVED TO INSPECT
12/06/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
11/14/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 120' 7 - 4" PVC SESDS
BUILDING WEST
11/08/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK PVC UNDER NORTHEAST SECTION
11/06/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK PVC CONDUIT AT NORTH ELEVATOR SHAFT
11/02/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK SOUTHEAST SECTION & HALF TO NORTH FROM SOUTH
11/01/2007 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
10/31/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 8 - 4" TEP TO SES
1 - 2" TEMP POWER
1 - 3/4" CARPORT
PVC CONTINUATION FROM SOUTHEAST
10/30/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 180' EAST OF ELEVATOR AT SOUTHEAST SECTION
10/29/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK PVC CONDUITS UNDER SLAB
NORTHWEST SECTION
10/18/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK PVC CONDUITS IN ELECTRIC ROOM UNDERSLAB AT SOUTHWEST CORNER OF BUILDING
10/17/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK PVC CONDUITS SOUTHWEST 1/2 UNDER SLAB EXCLUDING ELECTRIC ROOM
10/12/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 7 - 4" PVC TEP TO SES "D"
10/11/2007 ELECTRIC - UNDERGROUND Cancelled IVRS - RI canceled
10/11/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK PVC CONDUITS SOUTHEAST 1/2 UNDER SLAB
10/02/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
09/28/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 90 DEG. STUBS INTO SECTION

*NOTE: 352.46 WILL APPLY
09/27/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
FINISH CONDUITS
OK PVC CONDUITS TO SES FROM LAST INSPECTION
09/26/2007 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
09/24/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 2 1/2" & 3" PVC FEEDERS WEST 2/3"