Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/14/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/21/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED TO VERIFY GROUNDING TIE IN AT MCC UNIT ON NEW FEEDS. 2. DOOR TO BE INSTALLED ON MCC 3. WIRING TO BE FINISHED ON 400A CHILLER BREAKER WHERE WIRING NOT CONNECTED, NEED TO SEE WIRING METHOD. |