Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/11/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) WORK DONE OK SUBJECT TO PLANS 2) PLAN REVISION TO BE REFLECTIVE OF WORK INSTALLED AND EXISTING |
|
| 05/01/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20 2. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING 250.8 3. PLEASE PROVIDE LETTER FOR ADDED LIGHTS & DELETED OUTLETS & WATER HEATER & OUTLETS 4. EM/EXIT LIGHTS TO BE ON AREA SERVED 700.12 5. PANEL SCHEDULE TO BE LABELED AS PER 408.4 NO ABBREVIATIONS. 6. PLEASE VACATE AREAS TO INSPECT ELECTRICAL AREAS OCCUPIED WITHOUT INSPECTIONS. |