Permit: T06CM06098

Parcel: 12213035B

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/11/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) WORK DONE OK SUBJECT TO PLANS
2) PLAN REVISION TO BE REFLECTIVE OF WORK INSTALLED AND EXISTING
05/01/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20
2. SHEETMETAL SCREWS NOT ALLOWED FOR
GROUNDING 250.8
3. PLEASE PROVIDE LETTER FOR ADDED LIGHTS & DELETED OUTLETS & WATER HEATER & OUTLETS
4. EM/EXIT LIGHTS TO BE ON AREA SERVED 700.12
5. PANEL SCHEDULE TO BE LABELED AS PER 408.4 NO ABBREVIATIONS.
6. PLEASE VACATE AREAS TO INSPECT ELECTRICAL

AREAS OCCUPIED WITHOUT INSPECTIONS.