Permit: T06CM06019

Parcel: 138240860


Addresses:

1485 W COMMERCE CT

Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Date Description Inspector Results Comments
10/30/2007 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection :*
10/16/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
4' EAST BLD & WEST BLD SCREEN WALLS OK
10/03/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
OK TO POUR BACK SLAB @ STEEL COLS.
09/24/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
12' @ INFILL OK/OK TO TAP WITH SP. INSPECTION
REBAR MUST EXTEND INTO BOND BEAM
09/21/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
4' @ INFILL
BOB -- OK TO LINTEL IF SPECIAL INSP. COMES BACK & VERIFIES
09/19/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
09/18/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
16' WEST BUILDING WHEN SP. INSP. CONFIRMS
1. VERTS TO EXTEND AT LEAST 2/3 INTO TOP BOND BEAM
2. MISSING SEVERAL VERTS @ MCJ'S

TOP OUT AT EAST BLD. OK
09/17/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1. VERTS MUST BE 2/8 INTO TOP COURSE
2. NO LAPS WITHIN 8' OF MLU
09/14/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
09/13/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
OK TO 12'8" WHEN SPECIAL INSP. CONFIRMS
09/12/2007 REINFORCED MASONRY PRE-GROUT Cancelled IVRS - RI canceled
09/11/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
8' @ N & 1/2 WEST
09/07/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
BLDG #2 CMU WALLS - TOPOUT @ 20' 8 INCH
BLDG #1 1ST LIFT TO 4 FOOT AT ENTIRE PERIMETER CMU WALLS SPECIAL INSPECTOR VIEWED & ACCEPTED ABOVE.
09/05/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
BUILDING B
TOP F.5/2B-5B; 3RD LIFT N 1/2 ALL 4TH LIFT LINE K 5 1/2 & 5B
08/31/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
12' PERIMETER
08/29/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1. YOU MUST HAVE SPECIAL INSPECTION DURING GROUTING
2. YOU MUST CONSOLIDATE GROUT PER STANDARDS FROM
ACI 8' AROUND PERIMETER OK
08/28/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
8' ALL AROUND WHEN SPECIAL INSP. CONFIRMS N END
08/23/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EAST BLD. N & E WALLS TO 4'