Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/22/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP. 2. SUPPORT PVC AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES, THEN NO MORE THAN FOUR FEET BETWEEN HANGERS. 3. REQUIRE 18" OF COPPER AT SERVICE AND AT WATER HEATER 4. DRAINAGE FITTINGS ON VENTS BELOW 42" |
|