Permit: T06CM05990

Parcel: 103191550

Inspection Status: Not ready for Inspection

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
06/22/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP.
2. SUPPORT PVC AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES, THEN NO MORE THAN FOUR FEET BETWEEN HANGERS.
3. REQUIRE 18" OF COPPER AT SERVICE AND AT WATER HEATER
4. DRAINAGE FITTINGS ON VENTS BELOW 42"
06/22/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
CORRECTIONS MADE OK
OK TO COVER ALL AREAS